Module RS-485 DCON & Modbus 8 kênh đầu ra Relay ICP DAS M-7069D
Features
- M-7068(D)
- 4 Form A and 4 Form C Signal Relay Output
- 2000 VDC Intra-module Isolation
- M-7069(D)
- 4 Form A and 4 Form C Power Relay Output
- 3750 VDC Intra-module Isolation
- Dual Watchdog
- 4 kV ESD Protection
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
- Wide Operating Temperature Range: -25 ~ +75°C
Introduction
The M-7068 provides 4 Form A signal relay output channels and 4 Form C signal relay output channels, while the M-7069 provides 4 Form A power relay output channels and 4 Form C power relay output channels. Both include 8 LED indicators that can be used to monitor the relay output status, and options are provided that allow power-on and safe digital output values to be configured. 4 kV ESD, 4 kV EFT and 3 kV surge protection are also provided to enhance noise protection capabilities in industrial environments. The M-7068 is the ideal solution for small signal switching, while the M-7069 is the ideal solution for high power applications.
Application
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
System Specification
| Model | M-7068 | M-7068D | M-7069 | M-7069D |
| Communication | ||||
| Interface | RS-485 | |||
| Bias Resistor | No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) | |||
| Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), (O, 8, 1) | |||
| Baud Rate | 1200 ~ 115200 bps | |||
| Protocol | Modbus RTU, DCON | |||
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) | |||
| LED Indicator/Display | ||||
| System LED Indicator | Yes, 1 LED as Power/Communication Indicator | |||
| I/O LED Indicator | – | Yes, 8 LEDs as Relay Output Indicators |
– | Yes,8 LED as Relay Output Indicator |
| 7-Segment LED Display | – | |||
| Isolation | ||||
| Intra-module Isolation, Field-to-Logic | 2000 VDC | 3750 VDC | ||
| EMS Protection | ||||
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal ±8 kV Air for Random Point |
|||
| EFT (IEC 61000-4-4) | ±4 kV for 8 Relay and Power Line ±2 kV for RS-485 Port Line |
|||
| Surge (IEC 61000-4-5) | ±3 kV for Power | |||
| Power | ||||
| Reverse Polarity Protection | Yes | |||
| Input Range | 10 ~ 30 VDC | |||
| Consumption | 1.6 W (Max.) | 2.0 W (Max.) | 2.1 W (Max.) | 2.5 W (Max.) |
| Mechanical | ||||
| Dimensions (W x L x H) | 72 mm x 123 mm x 35 mm | |||
| Installation | DIN-Rail or Wall Mounting | |||
| Environment | ||||
| Operating Temperature | -25 ~ +75°C | |||
| Storage Temperature | -40 ~ +85°C | |||
| Humidity | 10 ~ 95% RH, Non-condensing | |||
I/O Specification
| Model | M-7068 | M-7068D | M-7069 | M-7069D | |
| Relay Output | |||||
| Channels | 8 (Form A × 4, Form C × 4) | ||||
| Relay Type | Signal Relay | Power Relay | |||
| Form A | Contact Rating | 2 A @ 30 VDC 0.24 A @ 220 VDC 0.25 A @ 250 VAC |
6 A @ 35 VDC 6 A @ 240 VAC |
||
| Min. Contact Load | 10 mA @ 20 mV | 100 mA @≧ 12 V | |||
| Contact Material | Silver Nickel, Gold-covered | Silver Cadmium Alloy | |||
| Operate Time | 3 ms (typical) | 5 ms (typical) | |||
| Release Time | 4 ms (typical) | 1 ms (typical) | |||
| Mechanical Endurance | 108 ops | 30 X 106 ops | |||
| Electrical Endurance | 2 X 105 ops | 1 X 105 ops | |||
| Form C | Contact Rating | 2 A @ 30 VDC 0.24 A @ 220 VDC 0.25 A @ 250 VAC |
5 A @ 30 VDC 5 A @ 250 VAC |
||
| Min. Contact Load | 10 mA @ 20 mV | 100 mA @≧ 12 V | |||
| Contact Material | Silver Nickel, Gold-covered | Silver Nickel Alloy | |||
| Operate Time | 3 ms (typical) | 5 ms (typical) | |||
| Release Time | 4 ms (typical) | 2 ms (typical) | |||
| Mechanical Endurance | 108 ops | 15 X 106 ops | |||
| Electrical Endurance | 2 X 105 ops | 1 X 105 ops | |||
| Surge Strength | 2000 VDC | 4000 VDC | |||
| Power-on Value | Yes | ||||
| Safe Value | Yes | ||||
Ordering information
| M-7068-G CR | 4-channel Form A Signal Relay Output and 4-channel Form C Signal Relay Output Module (Gray Cover) (RoHS) |
| M-7068D-G CR | M-7068 with LED Display (Gray Cover) (RoHS) |
| M-7069-G CR | 4-channel Form A Power Relay Output and 4-channel Form C Power Relay Output Module (Gray Cover) (RoHS) |
| M-7069D-G CR | M-7069 with LED Display (Gray Cover) (RoHS) |