Module RS-485 DCON & Modbus 8 kênh đầu vào số (DI) + 8 kênh đầu ra số (DO) ICP DAS M-7055UD
Features
- Digital Input and Digital Output selectable as either sink- or source-type via wire connection.
- All Digital Input Channels can be used as 16-bit Counters
- Built-in Dual Watchdog
- 8 kV ESD Protection
- 2000 VDC Intra-module Isolation
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
- Wide Operating Temperature Range: -25 to +75°C
Introduction
The M-7055U module provides 8 isolated channels for Digital Input and 8 isolated channels for Digital Output. Digital Input and Digital Output can be selected as either sink- or source-type via wire connection. All Digital Input channels are also able to be used as 16-bit counters. There are options to enable both power-on and safe values. The M-7055UD has 16 LED indicators that can be used to monitor the status of the Digital Input and Digital Output channels. The M-7055U(D) also provides ±8 kV ESD, ±4 kV EFT and ±2 kV surge protection, as well as 2000 VDC intra-module isolation to enhance noise protection capabilities in harsh industrial environments.
System Specification
| Models | M-7055U | M-7055UD |
| Communication | ||
| Interface | RS-485 | |
| RS-485 Bias Resistor | No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) | |
| Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), (O, 8, 1) | |
| Baud Rate | 1200 to 115200 bps | |
| Protocol | Modbus RTU, DCON | |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) | |
| LED Indicator/Display | ||
| System LED Indicator | Yes, 1 as Power/Communication Indicator | |
| I/O LED Indicator | – | Yes, 8 as Digital Input Indicators and 8 as Digital Output Indicators |
| 7-Segment LED Display | – | |
| Isolation | ||
| Intra-Module Isolation, Field-to-Logic | 2000 VDC | |
| EMS Protection | ||
| ESD (IEC 61000-4-2) | ±8 kV Contact for each Terminal | |
| ±15 kV Air for Random Point | ||
| EFT (IEC 61000-4-4) | ±4 kV for Power Line | |
| Surge (IEC 61000-4-5) | ±2 kV | |
| Power | ||
| Reverse Polarity Protection | Yes | |
| Input Range | 10 ~ 48 VDC | |
| Consumption | 0.9 W (Max.) | 1.0 W (Max.) |
| Mechanical | ||
| Dimensions (L x W x H) | 123 mm x 72 mm x 35 mm | |
| Installation | DIN-Rail or Wall Mounting | |
| Environment | ||
| Operating Temperature | -25 to +75°C | |
| Storage Temperature | -40 to +85°C | |
| Humidity | 10 to 95% RH, Non-condensing | |
I/O Specification
| Models | M-7055U | M-7055UD | |
| Digital Input/Counter | |||
| Channels | 8 | ||
| Type | Dry Contact | Source | |
| Wet Contact | Sink/Source | ||
| Wet Contact | ON Voltage Level | +10 ~ 50 VDC | |
| OFF Voltage Level | +4 VDC Max. | ||
| Dry Contact | ON Voltage Level | Close to GND | |
| OFF Voltage Level | Open | ||
| Counters | Max. Count | 65535 (16-bit) | |
| Max. Input Frequency | 100 Hz | ||
| Min. Pulse Width | 5 ms | ||
| Input Impedance | 10 kΩ | ||
| Channel-to-Channel Isolation | – | ||
| Overvoltage Protection | ±70 VDC | ||
| Digital Output | |||
| Channels | 8 | ||
| Type | Push-Pull | ||
| Sink/Source (NPN/PNP) | Sink/Source | ||
| Load Voltage | +3.5 ~ 80 VDC | ||
| Max. Load Current | 500 mA / Channel | ||
| Overvoltage Protection | – | ||
| Short Circuit Protection | – | ||
| Power-on Value | Yes | ||
| Safe Value | Yes | ||
Ordering information
| M-7055U-G CR | 8-channel Isolated Digital Input and 8-channel Isolated Digital Output Module, Sink- or Source-type selectable via Wire Connection (Gray Cover) (RoHS) |
| M-7055UD-G CR | M-7055U with LED Display (Gray Cover) (RoHS) |