Module RS-485 Modbus & DCON 2 kênh đầu vào 4-Wire Full-Bridge Strain Gauge + 4 DO + 1 DO ICP DAS M-7016
Features
- 2-channel Strain Gauge Measurement
- High Resolution: 16-bit
- Excitation Voltage Output: 0 ~ +10 V
- 50 Hz Event Counter (Digital Input)
- High/Low Alarm (Digital Output)
- Linear Mapping Function
- 3000 VDC Intra-module Isolation
- Dual Watchdog
- Wide Operating Temperature Range: -25 to +75°C
Introduction
In the industrial environment, there are numerous examples where force needs to be converted into a measurable electrical output. In most cases, a strain gauge or a load cell can be used. But the question is, how do we then deal with these electrical output measurements? In this situation, the I-7016 is definitely the No. 1 choice. Not only can the module process data from a load cell or a strain gauge, it also features linear mapping that can be used to directly convert the resulting data into weight via a user-defined correspondent table. The I-7016 supports full-bridge strain gauges and provides 2 Analog Input channels, 1 excitation voltage output channel, 1 Digital Input channels and 4 Digital Output channels. The module provides a programmable input range (±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, and ±2.5 V) and each Analog Input channel can be individually configured. Excitation voltage output can be in the range of 0 ~ +10 V, with a 40 mA driving efficiency. Digital Output channels can also be set as high or low alarm outputs. The M-7016 supports both the Modbus RTU and DCON protocols, which can be configured via software, and all hardware specifications are the same as the I-7016.
Application
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
I/O Specification
| Models | I-7016 | I-7016D | M-7016 | M-7016D |
| Strain Gauge Input | ||||
| Channels | 2 | |||
| Wiring | 4-wire | |||
| Sensor Types | Full-Bridge | |||
| Resolution | 16-bit | |||
| Accuracy | ±0.05% of FSR | |||
| Sampling Rate | 10 Hz for 1-channel mode or 2 Hz (total) for 2-channel mode | |||
| Input Impedance | 20 MΩ | |||
| Individual Channel Configuration | – | |||
| Overvoltage Protection | ±5 VDC | |||
| Open Wire Detection | – | |||
| Long Distance Measurement | – | |||
| Excitation Voltage Output | ||||
| Channels | 1 | |||
| Range | 0 ~ +10 V | |||
| Max. Load Current | 40 mA | |||
| Resolution | 16-bit | |||
| Accuracy | ±0.05% | |||
| Power-on Value | Yes | |||
| Digital Input | ||||
| Channels | 1 | |||
| Contact | Dry | |||
| Sink/Source (NPN/PNP) | Source | |||
| ON Voltage Level | Close to GND | |||
| OFF Voltage Level | Open | |||
| Counter (50 Hz, 16-bit) | Yes | |||
| Input Impedance | 3 kΩ | |||
| Overvoltage Protection | ±30 VDC | |||
| Digital Output | ||||
| Channels | 4 | |||
| Type | Open Collector | |||
| Sink/Source (NPN/PNP) | Sink | |||
| Load Voltage | +3.5 ~ +50 VDC | |||
| Max. Load Current | 30 mA/Channel | |||
| Power-on Value | Yes | |||
| Safe Value | Yes | |||
System Specification
| Models | I-7016 | I-7016D | M-7016 | M-7016D |
| Communication | ||||
| Interface | RS-485 | |||
| Bias Resistor | No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) | |||
| Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) | |||
| Baud Rate | 1200 to 115200 bps | |||
| Protocol | DCON | Modbus RTU, DCON | ||
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) | |||
| LED Indicator/Display | ||||
| System LED Indicator | Yes, 1 as Power/Communication Indicator | |||
| I/O LED Indicator | – | |||
| 7-Segment LED Display | – | Yes | – | Yes |
| Isolation | ||||
| Intra-Module Isolation, Field-to-Logic | 1500 VDC | |||
| EMS Protection | ||||
| ESD (IEC 61000-4-2) | – | |||
| EFT (IEC 61000-4-4) | – | |||
| Surge (IEC 61000-4-5) | – | |||
| Power | ||||
| Reverse Polarity Protection | Yes | |||
| Input Range | +10 ~ +30 VDC | |||
| Consumption | 2.4 W | 3.0 W | 2.4 W | 3.0 W |
| Mechanical | ||||
| Dimensions (L x W x H) | 123 mm x 72 mm x 35 mm | |||
| Installation | DIN-Rail or Wall Mounting | |||
| Environment | ||||
| Operating Temperature | -25 to +75°C | |||
| Storage Temperature | -40 to +85°C | |||
| Humidity | 10 to 95% RH, Non-condensing | |||
Ordering information
| I-7016 CR | 2-channel Strain Gauge Input Module using the DCON Protocol (Blue Cover) (RoHS) |
| I-7016D CR | I-7016 with 7-segment LED Display (Blue Cover) (RoHS) |
| I-7016D-G CR | I-7016 with 7-segment LED Display (Gray Cover) (RoHS) |
| M-7016-G CR | 2-channel Strain Gauge Input Module using the DCON and Modbus Protocols (Gray Cover) (RoHS) |