Module 16 kênh đầu vào số (DI) cách ly ICP DAS I-9053P CR
Features
• 16-channel Digital Input
• Channel Status LED Indicators
• Compatible with 24 V Levels
• Long Distance Measurement
• Dry and Wet Contact, Selectable via Wire Connections
• 3750 Vrms Intra-module Isolation
• Wide Operating Temperature Range : -25 ~ +75°C
Introduction
The I-9053P offers 16 channels for digital input, catering for both dry and wet contact, with an effective distance for dry contact of up to 500 meters. All channels feature photocouple isolation. The I-9053P provides 16 LED indicators that can be used to monitor the DI channel status. 4 kV ESD protection and 3750 Vrms intramodule isolation are also provided to enhance noise immunity capabilities in industrial environments.
Specifications
| Isolation | |
|---|---|
| Intra-module Isolation | 3750 VDC |
| EMS Protection | |
|---|---|
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal ±8 kV Air for Random Point |
| LED Indicators | |
|---|---|
| Status | 1 x Power and Communication 16 x DI |
| Digital Input | |
|---|---|
| Channels | 16 |
| Type | Dry + Wet Contact |
| Sink/Source (NPN/PNP) | Sink/Source |
| ON Voltage Level | Dry: Close to GND Wet: +19 VDC ~ +30 VDC |
| OFF Voltage Level | Dry: Open Wet: +11 VDC Max. |
| Response Speed | OFF to ON: 1 ms/5 ms/10 ms/20 ms/40 ms/70 ms (by Jumper select) or CPU parameter setting, Default Setting is 10 ms ON to OFF: 1 ms/5 ms/10 ms/20 ms/40 ms/70 ms (by Jumper select) or CPU parameter setting, Default Setting is 10 ms |
| Low Pass Filter | Yes, Programmable |
| Effective Distance | 500 m Max. |
| Power | |
|---|---|
| Consumption | 1 W Max. |
| Mechanical | |
|---|---|
| Dimensions (mm) | 31 x 134 x 144 (W x L x H) |
| Environment | |
|---|---|
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Ordering information
| I-9053P CR | 16-ch Isolated DI (Dry, Wet) Module with Low Pass Filter (RoHS) |