Module 8 kênh đầu vào số, 8 kênh đầu ra số ICP DAS I-87054W
Features
- 8-channel Isolated Digital Input and 8-channel Isolated Digital Output
- Sink-type Digital Output Channels with Overload Protection
- All Digital Input Channels can be used as 16-bit Counters
- Short-circuit and Overcurrent Protection
- 4 kV ESD Protection
- 3750 VDC Intra-module Isolation
- Configurable Power-on Value
- Configurable Safe Value
- RoHS Compliant
- Wide Operating Temperature Range: -25 to +75°C
Introduction
The I-87054W module offers 8 isolated Digital Input channels and 8 isolated Digital Output channels. Either sink- or source-type Digital Input can be selected via the wire connections, and all Digital Input channels are also able to be used as 16-bit counters. The I-87054W supports sink-type output with short circuit protection. The I-87054W includes 16 LED indicators that can be used to monitor the status of the Digital Input and Digital Output channels, and options are available for configuring both power-on and safe values. 4 kV ESD protection and 3750 VDC intra-module isolation are provided as standard.
Applications
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
I/O Specifications
| Digital Input | ||
| Channels | 8 | |
| Type | Wet Contact | |
| Sink/Source (NPN/PNP) | Sink, Source | |
| ON Voltage Level | +3.5 VDC ~ +50 VDC | |
| OFF Voltage Level | +1 VDC Max. | |
| Input Impedance | 10 kΩ, 0.66 W | |
| Counters | Channels | 8 |
| Max. Count | 16-bit (65535) | |
| Max. Input Frequency | 100 Hz | |
| Min. Pulse Width | 5 ms | |
| Channel-to-Channel Isolation | Yes | |
| Low Pass Filter | Yes | |
| Effective Distance for Dry Contact | – | |
| Digital Output | ||
| Channels | 8 | |
| Type | Open Collector | |
| Sink/Source (NPN/PNP) | Sink | |
| Load Voltage | +5 VDC ~ +50 VDC | |
| Max. Load Current | 700 mA/channel | |
| Overvoltage Protection | 60 VDC | |
| Overload Protection | Yes | |
| Short-circuit and Overcurrent Protection | Yes, 1.4 A | |
| Power-on Value | Yes | |
| Safe Value | Yes | |
System Specifications
| Communication | |
| Interface | RS-485 |
| Format | N, 8, 1 |
| Baud Rate | 1200 to 115200 bps |
| Protocol | DCON |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicators/Display | |
| System LED Indicator | Yes, 1 as Power/Communication Indicator |
| I/O LED Indicators | 16 as High/Low Alarm Signals |
| Isolation | |
| Intra-module Isolation, Field-to-Logic | 3750 Vrms |
| EMS Protection | |
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
| ±8 kV Air for Random Point | |
| Power | |
| Power Consumption | 0.7 W Max. |
| Mechanical | |
| Dimensions (L x W x H) | 115 mm x 30 mm x 102 mm |
| Environment | |
| Operating Temperature | -25 to +75°C |
| Storage Temperature | -40 to +85°C |
| Humidity | 10 to 95% RH, Non-condensing |
Ordering information
| I-87054W-G CR | 8-channel Isolated Digital Input and 8-channel Isolated Digital Output Module using the DCON Protocol (Gray Cover) (RoHS) |
Accessories
| RM-104/108/116 | 4/8/16-channel 16 A Power Relay Board, 1 Form C |
| RM-204/208/216 | 4/8/16-channel 8 A Power Relay Board, 2 Form C |
| DN-SSR4 | 4-channel 1A Solid-state Relay Board, 1 Form A |
| RM-22.22 | 1-channel 20 A Power Relay for Direct 35 mm Rail (EN 50022) Mounting, 2 Form A |