Module 4 kênh đầu ra tương tự ICP DAS I-87024CW
Features
- I-87024UW
- 4-channel Voltage or Current Output
- Individual Channel Configuration
- 2500 VDC Intra-module Isolation
- I-87024CW
- 1 kV Channel-to-Channel Isolation
- Open Wire Detection for Current Output
- RF Immunity
- Short Circuit Protection
- Power-on Value
- Safe Value
- 4 kV ESD Protection
- Wide Operating Temperature Range: -25 ~ +75°C
Introduction
The I-87024CW is a 4-channel current output module that features channel-to-channel isolation and also has qualification for 4 KV ESD protection and 1000 VDC intra-module isolation. Options for configuring power-on and safe values are also included.
The I-87024UW is a source type analog output module that includes 4 single-ended analog output channels, and provides options for setting power-on and safe value. It also provides a programmable output range analog outputs(0 ~ 5 V, +/-5 V, 0 ~ 10 V, +/-10 V, +4 ~ +20 mA or 0 ~ +20 mA), and each analog output can be configured for an individual range and provides an RF immunity level matching that defined by IEC 61000-4-3. The module also features per-channel open wire detection for +4 ~ +20 mA output, together with 4 KV ESD protection as well as 2500 VDC intra-module isolation.
Applications
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment.
I/O Specifications
| Model | I-87024CW | I-87024UW | |
| Analog Output | |||
| Channels | 4 | ||
| Current Output Wiring | Sink | Source | |
| Range | 0 ~ +20 mA, +4 ~ +20 mA |
0 ~ +5 VDC, ±5 VDC, 0 ~ +10 VDC, ±10 VDC, 0 ~ +20 mA, +4 ~ +20 mA |
|
| Resolution | 12-bit | 16-bit | |
| Accuracy | +/- 0.1% of FSR | +/- 0.02% of FSR | |
| Zero Drift | +/- 0.2 μV/°C | ||
| Span Drift | +/- 25 ppm/°C | ||
| DA Output Respones Time | 10 ms per channel | ||
| Programmable Output Slope |
Voltage | – | 0.0625 ~ 512 V/Second |
| Current | 0.125 ~ 1024 mA/Second | ||
| Current Output Capacity | External +24 VDC @ 1050 Ω | 1000 Ω | |
| Channel-to-Channel Isolation | Yes, 1 kV | – | |
| Open Wire Detection | Yes, +4 ~ +20 mA | ||
| Short Circuit Protection | Yes | ||
| Power-on Value | Yes | ||
| Safe Value | Yes | ||
| External Power Requirements | |||
| Reverse Polarity Protection | – | Yes | |
| Powered from Terminal Block | – | Yes, 15 ~ 30 VDC | |
| Consumption | – | 4.0 W | |
Systerm Specifications
| Model | I-87024CW | I-87024UW |
| Communication | ||
| Interface | RS-485 | |
| Format | N, 8, 1 | |
| Baud Rate | 1200 ~ 115200 bps | |
| Protocol | DCON | |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) | |
| LED Indicator/Display | ||
| System LED Indicator | 1 LED as Power/Communication Indicator | |
| I/O LED Indicator | 16 LEDs as High/Low Alarm Signals | – |
| Isolation | ||
| Intra-Module Isolation, Field-to-Logic |
1000 VDC | 2500 VDC |
| EMS Protection | ||
| ESD (IEC 61000-4-2) | 4 kV Contact for Each Terminal | |
| 8 kV Air for Random Point | ||
| RS Immunity (IEC 61000-4-3) | – | 3 V/m, 80 MHz ~ 1 GHz |
| Power | ||
| Power Consumption | 0.9 W Max. | |
| Mechanical | ||
| Dimensions (W x L x H) | 31 mm x 81 mm x 114 mm | |
| Environment | ||
| Operating Temperature | -25 ~ +75 °C | |
| Storage Temperature | -40 ~ +85°C | |
| Humidity | 10 ~ 95% RH, Non-condensing | |
Ordering Informations
| I-87024CW-G CR | 4-channel 12-bit Channel-to-Channel Isolated Current Output Module with Open-wire Detection (Gray Cover) (RoHS) |
| I-87024UW-G CR | 4-channel 16-bit Isolated Source Type Voltage or Current Output Module (Gray Cover) (RoHS) |
Accessories
| SG-770 CR | 7-channel Differential or 14-channel Single-ended Surge Protector (RoHS) |