Module RS-485 DCON 5 kênh đầu ra Relay + 4 kênh đầu vào số (DI) ICP DAS I-7065D
Features
- I-7063(D)
- 8 Digital Input channels and 3 Relay Output channels
- I-7065(D) and M-7065(D)
- 4 Digital Input channels and 5 Relay Output channels
- Form A Power Relay Output
- Sink- and Source-type for Digital Input
- Digital Input Channels can be used as 16-bit Counters
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
- Dual Watchdog
- Wide Operating Temperature Range: -25 ~ +75°C
Introduction
The I-7063 module provides 8 digital input channels and 3 Form A relay output channels, and the 7065 series provides 4 digital input channels and 5 Form A relay output channels. All digital input channels can be used as 16-bit counters. In addition, the digital input channels can be selected either as sink- or source-type via wire connections. The I-7063D provides 11 LED indicators and the I-7065D/M-7065D provides 9 LED indicators that can be used to monitor the status of the digital input and relay output. The M-7065 supports both the Modbus RTU and DCON protocols, which can be configured via software. There are also options for configuring power-on and safe values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided to enhance noise protection capabilities in industrial environments.
Application
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
System Specification
| Models | I-7063 | I-7063D | I-7065 | I-7065D | M-7065 | M-7065D |
| Communication | ||||||
| Interface | RS-485 | |||||
| Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) | |||||
| Baud Rate | 1200 ~ 115200 bps | |||||
| Protocol | DCON | Modbus RTU, DCON | ||||
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) | |||||
| LED Indicator/Display | ||||||
| System LED Indicator | Yes, 1 LED as Power/Communication Indicator | |||||
| I/O LED Indicators | – | Yes, 11 LEDs as Digital Input/ Relay Output Indicators |
– | Yes, 9 LEDs as Digital Input/ Relay Output Indicators |
– | Yes, 9 LEDs as Digital Input/Relay Output Indicators |
| 7-Segment LED Display | – | |||||
| Isolation | ||||||
| Intra-Module Isolation, Field-to-Logic | 3750 VDC | |||||
| EMS Protection | ||||||
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal | |||||
| ±8 kV Air for Random Point | ||||||
| EFT (IEC 61000-4-4) | ±2 kV for Power Line | |||||
| Surge (IEC 61000-4-5) | – | |||||
| Power | ||||||
| Reverse Polarity Protection | Yes | |||||
| Input Range | 10 ~ 30 VDC | |||||
| Consumption | 0.9 W | 1.4 W | 1.3 W | 1.8 W | 1.3 W | 1.8 W |
| Mechanical | ||||||
| Dimensions (W x L x H) | 72 mm x 123 mm x 35 mm | |||||
| Installation | DIN-Rail or Wall Mounting | |||||
| Environment | ||||||
| Operating Temperature | -25 ~ +75°C | |||||
| Storage Temperature | -40 ~ +85°C | |||||
| Humidity | 10 ~ 95% RH, Non-condensing | |||||
I/O Specification
| Models | I-7063/I-7063D | I-7065/I-7065D | M-7065/M-7065D | |
| Relay Output | ||||
| Channels | 3 | 5 | ||
| Relay Type | Power Relay | |||
| Form A Relay | Contact Rating | 5 A @ 250 VAC 5 A @ 30 VDC |
||
| Min. Contact Load | 10 mA @ 5 V | |||
| Contact Material | Gold-plated Silver Cadmium Alloy | |||
| Operate Time | 6 ms | |||
| Release Time | 3 ms | |||
| Mechanical Endurance | 2 × 107 ops. | |||
| Electrical Endurance | 1 × 105 ops. | |||
| Surge Strength | 4000 VDC | |||
| Power-on Value | Yes | |||
| Safe Value | Yes | |||
| Digital Input | ||||
| Channels | 8 | 4 | ||
| Type | Dry Contact | – | ||
| Wet Contact | Sink/Source | |||
| Wet Contact | On Voltage Level | +1 VDC Max. | ||
| Off Voltage Level | +4 ~ 30 VDC | |||
| Dry Contact | On Voltage Level | – | ||
| Off Voltage Level | – | |||
| Effective Distance for Dry Contact |
– | |||
| Counters | Max. Count | 65535 (16-bit) | ||
| Max. Input Frequency | 100 Hz | |||
| Min. Pulse Widt | 5 ms | |||
| Input Impedance | 3 kΩ | |||
| Channel-to-Channel Isolation | – | |||
| Overvoltage Protection | ±35 VDC | |||
Ordering information
| I-7063 CR | 8-channel Isolated Digital Input and 3-channel Relay Output Module using the DCON Protocol (Blue Cover) (RoHS) |
| I-7063D CR | I-7063 with LED Display (Blue Cover) (RoHS) |
| I-7065 CR | 4-channel Isolated Digital Input and 5-channel Relay Output Module using the DCON Protocol (Blue Cover) (RoHS) |
| I-7065-G CR | 4-channel Isolated Digital Input and 5-channel Relay Output Module using the DCON Protocol (Gray Cover) (RoHS) |
| I-7065D CR | I-7065 with LED Display (Blue Cover) (RoHS) |
| I-7065D-G CR | I-7065-G with LED Display (Gray Cover) (RoHS) |
| M-7065-G CR | 4-channel Isolated Digital Input and 5-channel Relay Output Module using the DCON and Modbus Protocols (Gray Cover) (RoHS) |
| M-7065D-G CR | M-7065-G with LED Display (Gray Cover) (RoHS) |