Module RS-485 DCON 1 kênh đầu vào 6-Wire Full-Bridge Strain Gauge + 4 DO + 1 DO ICP DAS I-7016P
Features
- Long-distance Strain Gauge Measurement
- High Resolution: 16-bit
- Excitation Voltage Output : 0 ~ +10 V
- 50 Hz Event Counter (Digital Input)
- High/Low Alarm (Digital Output)
- 3000 VDC Intra-module Isolation
- Dual Watchdog
- Wide Operating Temperature Range: -25 to +75°C
Introduction
The “P” version of the I-7016 module is another milestone in the development of the I-7016 series, and is a testament to excellence by the R&D team at ICP DAS. The I-7016P is specifically designed for long-distance strain gauge measurement, and provides 1 Digital Input channel as a 50 Hz event counter and 4 Digital Output channels that can act as high or low alarms. The I-7016P also features 3000 VDC intra-module isolation.
Application
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
I/O Specification
Models | I-7016P | I-7016PD |
Strain Gauge Input | ||
Channels | 1 | |
Wiring | 6-wire | |
Sensor Types | Full-Bridge | |
Resolution | 16-bit | |
Accuracy | ±0.05% of FSR | |
Sampling Rate | 10 Hz | |
Input Impedance | 20 MΩ | |
Individual Channel Configuration | – | |
Overvoltage Protection | ±5 VDC | |
Open Wire Detection | – | |
Long Distance Measurement | Yes | |
Excitation Voltage Output | ||
Channels | 1 | |
Range | 0 ~ +10 V | |
Max. Load Current | 40 mA | |
Resolution | 16-bit | |
Accuracy | ±0.05% | |
Power-on Value | Yes | |
Digital Input | ||
Channels | 1 | |
Contact | Dry | |
Sink/Source (NPN/PNP) | Source | |
ON Voltage Level | Close to GND | |
OFF Voltage Level | Open | |
Counter (50 Hz, 16-bit) | Yes | |
Input Impedance | 3 kΩ | |
Overvoltage Protection | ±30 VDC | |
Digital Output | ||
Channels | 4 | |
Type | Open Collector | |
Sink/Source (NPN/PNP) | Sink | |
Load Voltage | +3.5 ~ +50 VDC | |
Max. Load Current | 30 mA/Channel | |
Power-on Value | Yes | |
Safe Value | Yes |
System Specification
Models | I-7016P | I-7016PD |
Communication | ||
Interface | RS-485 | |
Bias Resistor | No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) | |
Format | N, 8, 1 | |
Baud Rate | 1200 to 115200 bps | |
Protocol | DCON | |
Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) | |
LED Indicator/Display | ||
System LED Indicator | Yes, 1 as Power/Communication Indicator | |
I/O LED Indicator | – | |
7-Segment LED Display | – | Yes |
Isolation | ||
Intra-Module Isolation, Field-to-Logic | 3000 VDC | |
EMS Protection | ||
ESD (IEC 61000-4-2) | 4 kV Contact for each Terminal | |
8 kV Air for Random Point | ||
EFT (IEC 61000-4-4) | ±4 kV for Power Line | |
Power | ||
Reverse Polarity Protection | Yes | |
Input Range | +10 ~ +30 VDC | |
Consumption | 1.3 W | |
Mechanical | ||
Dimensions (L x W x H) | 123 mm x 72 mm x 35 mm | |
Installation | DIN-Rail or Wall Mounting | |
Environment | ||
Operating Temperature | -25 to +75°C | |
Storage Temperature | -40 to +85°C | |
Humidity | 10 to 95% RH, Non-condensing |
Ordering information
I-7016P CR | 1-channel Strain Gauge Input Module using the DCON Protocol (6-wire) (Blue Cover) (RoHS) |
I-7016PD CR | I-7016P with 7-segment LED Display (6-wire) (Blue Cover) (RoHS) |