Bộ chuyển đổi Modbus RTU Slave sang M-Bus Master ICP DAS GW-7828
The M-Bus (“Meter-Bus”) is a standard for remote reading of meters. It is usable for most types of consumption meters as well as for various sensors and actuators. The GW-7828 is specially designed for M-Bus slave device. It offers Modbus RTU communication by three kinds of interface, RS-232, RS-422 and RS-485. On hardware the GW-7828 has two rotary switches for serial port and M-Bus port baud rate. GW-7828 supports Modbus RTU function code 0x03 and 0x04 to read data of M-Bus meters. Through this design, it is easy to communicate with any standard M-Bus slave.

Application
The M-Bus (Meter‐Bus) is a bus optimized for the reading of measurement instruments like: energy counters, hot and cold water counters, gas, pressure, sensors and actuators, etc.…

Features
- Supports M-Bus standard: EN-13757, CJ/T -188
- Supports Modbus RTU function code 0x03 and 0x04 to read Meter data
- Baud rate: Adjustable by rotary switch from 300 to 115200 bps
- Supports up to 100 M-Bus slaves
- M-Bus over current protection
- Short-circuit protection on the M-Bus
- Update firmware from serial port
- Provides PWR, MTX and MRX 3 LED indicators
Baud Rate Selection by Rotary Switch
| Switch Value | 0 | 1 | 2 | 3 | 4 | 5 |
| Baud [bps] | 300 | 600 | 1200 | 2400 | 4800 | 9600 |
| Switch Value | 6 | 7 | 8 | 9 | A ~ F | |
| Baud [bps] | 19200 | 38400 | 57600 | 115200 | User-defined | |
The data format of serial bus baud rate of switch value 0 ~ 9 is 8, n, 1.
The data format of M-Bus bus baud rate of switch value 0 ~ 3 is 8, e, 1
Execution Mode by DIP Switch
| DIP 1 (Init) | DIP 2 (Mode) | Description |
| OFF | OFF | Run Firmware |
| OFF | ON | Configure |
| ON | OFF | Update Firmware |
Utility
- Provide M-Bus and serial bus user-defined baud rate
- Check firmware version
- Configure meters list of M-Bus gateway
- Test reading meters data
- Update firmware

Support Meter
The following meters have been tested with the GW-7828 communication:
| Manufacture | Picture | Model Type | Meter Type |
| Danfoss | ![]() |
SONOMETER 500 | Heat Meter |
| SENSUS | ![]() |
405S | Water Meter |
| WESER | ![]() |
PUL | Heat Meter |
| DIEHL | ![]() |
ALTAIR V4 | Water Meter |
| Wason | ![]() |
LXZD-Y3 | Water Meter |
Hardware Specifications
| M-Bus Interface | |
| Channel | 1 |
| Baud Rate (bps) | 300 bps ~ 2400 bps |
| Data bit | 5, 6, 7, 8 |
| Stop bit | 1, 2 |
| Parity | None, Even, Odd, Space, Mark |
| Isolation | 3750 Vrms for photo-couple |
| ESD Protection | Contact ±4 kv class B |
| Current Protection | short-circuit protection |
| UART Interface | |
| Channel | 1 RS-232 / RS-422 / RS-485 (can’t be used simultaneously) |
| Baud Rate (bps) | 300 bps ~ 115200 bps |
| Data bit | 5, 6, 7, 8 |
| Stop bit | 1, 2 |
| Parity | None, Even, Odd, Space, Mark |
| ESD Protection | Contact ±4 kv class B |
| Power | |
| Power Supply | Unregulated +10 ~ +30 VDC |
| Protection | Power reverse polarity protection, Over-voltage brown-out protection |
| Power Consumption | 1.8 W @ 24 VDC (with 1 slave device) 11.8 W @ 24 VDC (with 100 slave devices) |
| Mechanical | |
| Installation | DIN-Rail |
| Dimension (W x L x H) | 72mm x 122mm x 33mm |
| Environment | |
| Operating Temperature | -25 to +60°C |
| Storage Temperature | -40 to +80°C |
| Relative Humidity | 10 to 90% RH, Non-condensing |
Ordering Information
|
GW-7828 CR
|
Modbus RTU Slave to M-Bus Master Gateway (RoHS) |