Bộ chuyển đổi Gateway Modbus TCP sang BACnet/IP ICP DAS GW-2439M
Features
- Read/Write BACnet objects via Modbus registers
- Configurable BACnet/IP Client
- Configurable Modbus TCP Server
- Supports BACnet AI, AO, AV, BI, BO, BV, MSI, MSO, MSV Object Types
- Supports Modbus discrete inputs, coils, input registers and holding registers
- Supports up to 500 DI/O and 1000 AI/O modbus registers to convert remote BACnet objects’ present value
- Simple data translation allows you to manipulate data as it passes between protocol
Introduction
GW-2439M is a network gateway allowing Modbus TCP client devices to be accessed BACnet/IP network as a BACnet/IP client. The BACnet/IP protocol is used to relay and exchange information between building devices. GW-2439M contains a large number of BACnet objects (AI, AO, AV, BI, BO, BV, MSI, MSO, MSV) gives you flexibility in mapping Modbus TCP registers to any combination of BACnet objects. BACnet interoperability building blocks (DS-RP-A, DS-RPM-A, DS-WP-A, DS-WPM-A, DM-DDB-A, DM-DOB-A, DM-DCC-A, DM-RD-A) are Supported. All the data transfer is configurable using ICPDAS Utility.
Application
- Building Automation
- Heating, Ventilating, and Air-conditioning Control
- Lighting Control
- Access Control
- Fire Detection Systems

Specification
| LED Indicators | |
|---|---|
| Status | Power (1), BACnet/IP Status (1), BACnet/IP Net(1), Modbus TCP TxD/RxD/Link (3) Ethernet LED Ethernet Status (RJ-45) (2) |
| BACnet/IP | |
|---|---|
| Modbus | BACnet/IP Client (Supports up to 32 stations) |
| Objects | AI, AO, AV, BI, BO, BV, MSI, MSO, MSV(Supports up to 500 DI/O and 1000 AI/O modbus registers to convert remote BACnet objects’ present value) |
| BIBBs | DS-RP-A, DS-RPM-A, DS-WP-A, DS-WPM-A, DM-DDB-A, DM-DOB-A, DM-DCC-A, DM-RD-A |
| Power | |
|---|---|
| Input Range | +10 ~ +30 VDC |
| Consumption | 5 W @ 24 VDC |
| Mechanical | |
|---|---|
| Casing | Metal |
| Dimensions (mm) | 33 x 120 x 116 |
| Installation | DIN-Rail |
| Environment | |
|---|---|
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Ordering information
| GW-2439M CR | Modbus TCP to BACnet/IP Gateway (RoHS) |