Module 2 cổng Ethernet Modbus TCP 3 kênh AI + 6 kênh DI + 3 kênh đầu ra Relay ICP DAS ET-7202
Features
- Built-in Web Server
- Web HMI
- Support for both Modbus TCP and Modbus UDP Protocols
- Communication Security
- 2-port Ethernet Switch for Daisy-Chain Topology
- Dual Watchdog
- Wide Operating Temperature Range: -25 ~ +75°C
- I/O Pair Connection
- Built-in I/O
- AI: 3 Channels with 240 Vrms Overvoltage Protection
- DI/Counter: 6 Channels
- Power Relay: 3 Channels
Introduction
The ET-7002/PET-7002/ET-7202/PET-7202 is a multi-function module with 3-channel analog inputs, 6-channel digital inputs and 3-channel relay outputs. It provides various programmable analog inputs (+/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V, +/-20 mA, 0 ~ 20 mA and 4 ~ 20 mA). Each analog input is allowed to configure a proper range with 240 Vrms high voltage protection. Each analog input can be programmed to accept current or voltage as input/output depending upon the position of corresponding jumper. The ET-7002/PET-7002/ET-7202/PET-7202 is fully RoHScompliant and has qualification for 4 kV ESD protection as well as 2500 VDC intra-module isolation.
Applications
System Specifications
Models | ET-7002 | PET-7002 | ET-7202 | PET-7202 |
Software | ||||
Built-In Web Server | Yes | |||
Web HMI | Yes | |||
I/O Pair Connection | Yes | |||
Communication | ||||
Ethernet Port | 1 x RJ-45, 10/100 Base-TX | 2 x RJ-45, 10/100 Base-TX, Swtich Ports | ||
PoE | – | Yes | – | Yes |
Protocol | Modbus TCP, Modbus UDP | |||
Security | ID, Password and IP Filter | |||
Dual Watchdog | Yes, Module (0.8 seconds), Communication (Programmable) | |||
LED Indicators | ||||
for System Running | Yes | |||
for Ethernet Link/Act | Yes | |||
for DI/DO status | – | Yes | ||
for PoE Power | – | Yes | – | Yes |
2 Way Isolation | ||||
Ethernet | 1500 VDC | – | 1500 VDC | – |
I/O | 2500 VDC | 2500 VDC | ||
EMS Protection | ||||
ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal and ±8 kV Air for Random Point | |||
EFT (IEC 61000-4-4) | ±4 kV for Power Line Line | ±2 kV for Power Line | ||
Surge (IEC 61000-4-5) | ±0.5 kV for Power Line | ±2 kV for Power Line | ||
Power | ||||
Reverse Polarity Protection | Yes | |||
Powered from Terminal Block | 10 ~ 30 VDC | 12 ~ 48 VDC | 12 ~ 48 VDC | 12 ~ 48 VDC |
Powered from PoE | – | Yes, IEEE 802.3af, Class1 | – | Yes, IEEE 802.3af, Class1 |
Consumption | 2.9 W (Max.) | 3.4 W (Max.) | 3.8 W (Max.) | 4.1 W (Max.) |
Mechanical | ||||
Dimensions (W x L x H) | 72 mm x 123 mm x 35 mm | 76 mm x 120 mm x 38 mm | ||
Installation | DIN-Rail or Wall mounting | |||
Environmental | ||||
Operating Temperature | -25 ~ +75 °C | |||
Storage Temperature | -30~ +80 °C | |||
Humidity | 10 ~ 90% RH, non-condensing |
I/O Specifications
Analog Input | |||
Channels | 3 (Differential) | ||
Type | +/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V +0 mA ~ +20 mA, +/-20 mA, 4 ~ 20 mA (jumper selectable) | ||
Individual Channel Configuration | Yes | ||
Resolution | 16-bit | ||
Sampling Rate | Normal Mode | 10 Samples/Second (Total) | |
Fast Mode | 50 Samples/Second (Total) | ||
Accuracy | Normal Mode | +/-0.1% | |
Fast Mode | +/-0.5% or better | ||
Zero Drift | +/-20 μV/°C | ||
Span Drift | +/-25 ppm/°C | ||
Overvoltage Protection | 240 Vrms | ||
Overcurrent Protection | 50 mA max. at 110 VDC/VAC max. | ||
Input Impedance | Voltage | 2 MΩ | |
Current | 125 Ω | ||
Common Mode Rejection | 86 dB Min. | ||
Normal Mode Rejection | 100 dB | ||
Open Wire Detection | Yes, for 4 ~ 20 mA only | ||
Virtual Channel to Channel Isolation | +/-400 VDC | ||
Digital Input/Counter | |||
Channels | 6 | ||
Contact | Wet Contact | ||
Sink/Source (NPN/PNP) | Sink/Source | ||
On Voltage Level | +10 VDC ~ +50 VDC | ||
Off Voltage Level | +4 VDC Max. | ||
Input Impedance | 10 KΩ, 0.5W | ||
Counters | Channels | 6 | |
Max. Count | 4,294,967,285 (32 bits) | ||
Max. Input Frequency | 100 Hz | ||
Min. Pulse Width | 5 ms | ||
Overvoltage Protection | +70 VDC | ||
Power Relay | |||
Channels | 3 | ||
Type | Power Relay, Form A (SPST N.O.) | ||
Operating Voltage Range | 250 VAC/30 VDC | ||
Max. Load Current | 5.0A/channel at 25°C | ||
Operate Time | 6 ms (Typical) | ||
Release Time | 3 ms (Typical) | ||
Electrical Life ( Resistive load ) | VDE: | 5 A @ 250 VAC 30,000 ops (10 ops/minute) at 75°C. | |
5 A @ 24 VDC 70,000 ops (10 ops/minute) at 75°C. | |||
UL: | 5 A @ 250 VAC/24 VDC 6,000 ops. | ||
3 A @ 250 VAC/24 VDC 100,000 ops. | |||
Mechanical Life | 20,000,000 ops. at no load (300 ops./minute). | ||
Intra-module Isolation, Field to Logic | 3750 VDC | ||
Power-on Value | Yes, Programmable | ||
Safe Value | Yes, Programmable |
Ordering information
ET-7002 CR | Ethernet I/O Module with 3-ch AI, 6-ch DI, 3-ch Relay (RoHS) |
PET-7002 CR | PoE Ethernet I/O Module with 3-ch AI, 6-ch DI, 3-ch Relay (RoHS) |
ET-7202 CR | Ethernet I/O Module with 2-port Ethernet Switch, with 3-ch AI, 6-ch DI, 3-ch Relay (RoHS) |
PET-7202 CR | PoE Ethernet I/O Module with 2-port Ethernet Switch, with 3-ch AI, 6-ch DI, 3-ch Relay (RoHS) |