Module RS-485 DCON & Modbus 16 kênh đầu ra xung PWM ICP DAS M-7088-16
Features
- 16-channel PWM Output
- Burst Mode and Continuous Mode for PWM Output
- Software Trigger Mode for PWM Output
- Individual and Synchronous PWM Output
- 4 kV ESD and EFT Protection
- Dual Watchdog
- Wide Operating Temperature Range: -25 to +75°C
Introduction
The M-7088-16 provides 16-channel PWM (Pulse Width Modulation) Output, and can be used to develop powerful and cost-effective analog control systems. PWM is a powerful technique for controlling analog circuits that uses the Digital Output to generate a waveform with a variable duty cycle and frequency which can then be used to control an analog circuit in applications such as controlling the position or speed of motors, the brightness of lamps, or the speed of fans, etc. Either burst mode or continuous mode can be used for the PWM output depending on the application. It supports both the Modbus RTU and the DCON protocols, and External PWR allows the load voltage to be increased from +3.5 to +50 V for the 16-channels PWM (Pulse Width Modulation) output.
Application
- Controlling Motor Position/Speed
- Dimming Lamp Brightness
- Controlling Fan Speed
System Specification
| Communication | |
| Interface | RS-485 |
| Bias Resistor | No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) |
| Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
| Baud Rate | 1200 to 115200 bps |
| Protocol | Modbus RTU, DCON |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicator/Display | |
| System LED Indicator | Yes, 1 as Power/Communication Indicator |
| I/O LED Indicator | – |
| 7-Segment LED Display | – |
| Isolation | |
| Intra-Module Isolation, Field-to-Logic | 2500 VDC |
| EMS Protection | |
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
| EFT (IEC 61000-4-4) | ±4 kV to Power |
| Surge (IEC 61000-4-5) | – |
| Power | |
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +48 VDC |
| Consumption | 2.9 W |
| Mechanical | |
| Dimensions (L x W x H) | 121 mm x 76 mm x 42 mm |
| Installation | DIN-Rail or Wall Mounting |
| Environment | |
| Operating Temperature | -25 to +75°C |
| Storage Temperature | -40 to +85°C |
| Humidity | 10 to 95% RH, Non-condensing |
I/O Specification
| Channels | 16 | |
| Type | PWM, TTL | |
| Sink/Source (NPN/PNP) | Sink | |
| Load Voltage | +5 ~ +50 VDC | |
| Max. Load Current | Sink | +50 VDC @ 200 mA/Channel |
| Source | – | |
| PWM | Frequency | 1 Hz ~ 500 KHz |
| Duty Cycle | 0.1 to 99.9% | |
| Mode | Burst, Continuous | |
| Burst Count | 1 to 65535 | |
| Trigger Start | Software | |
| Power-on Value | – | |
| Safe Value | – | |
Ordering information
| M-7088-16-G CR | 16-channel PWM Output Module using the DCON and Modbus Protocols (Gray Cover) (RoHS) |