Module RS-485 Modbus & DCON 1 kênh đầu ra tương tự ICP DAS M-7021A
Introduction
The I-7021 is a 12/16-bit, 1-channel Analog Output module that is designed for both voltage and current output. The I-7021 features 3000 VDC intra-module isolation, and the power source for the current output can be selected as either internal or external via a jumper. Options are also provided to allow power-on and safe values to be set. The M-7021A supports both the Modbus RTU and the DCON protocols which can be configured via software, and all hardware specifications are the same as the I-7021.
Features
- Current or Voltage Output
- High Resolution: 12-bit
- Software Selectable Current or Voltage Output
- Open Wire Detection for Current Output
- Readback Voltage or Current
- Configurable Power-on Value
- Configurable Safe Value
- 3000 VDC Intra-module Isolation
- Programmable Output Slope
- Dual Watchdog
- Wide Operating Temperature Range: -25 to +75°C
I/O Specification
| Models | I-7021 | I-7021P | M-7021A | |
| Analog Output | ||||
| Channels | 1 | |||
| Wiring | Unipolar | |||
| Range | Voltage | 0 ~ +10 V, | 0 ~ +5 V, 0 ~ +10 V, ±5 V, ±10 V |
|
| Current | 0 ~ +20 mA, +4 ~ +20 mA | |||
| Resolution | 12-bit | 16-bit | 12-bit | |
| Accuracy | 0.1% | 0.02% | 0.1% | |
| Readback Accuracy | ±0.5% of FSR | |||
| DA Output Response Time | 10 ms | |||
| Programmable Output Slope | Voltage | 0.0625 ~ 1024.0 V/Second | ||
| Current | 0.125 ~ 2048 mA/Second | |||
| Current Load Resistance | Internal Power: 500 Ω | |||
| External Power: 1050 Ω | ||||
| Open Wire Detection (for current only) | Yes | |||
| Channel-to-Channel Isolation | – | |||
| Short Circuit Protection | Yes | |||
| Power-on Value | Yes | |||
| Safe Value | Yes | |||
System Specification
| Models | I-7021 | I-7021P | M-7021A |
| Communication | |||
| Interface | RS-485 | ||
| RS-485 Bias Resistor | No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) | ||
| Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) | (N, 8, 1) | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
| Baud Rate | 1200 to 115200 bps | ||
| Protocol | DCON | Modbus RTU, DCON | |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) | ||
| LED Indicator/Display | |||
| System LED Indicator | Yes, 1 as Power/Communication Indicator | ||
| I/O LED Indicator | – | ||
| 7-Segment LED Display | – | ||
| Isolation | |||
| Intra-Module Isolation, Field-to-Logic |
3000 VDC | ||
| EMS Protection | |||
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal | ||
| EFT (IEC 61000-4-4) | ±4 kV to Power Line | ||
| Surge (IEC 61000-4-5) | ±0.5 kV for Power Line | ||
| Power | |||
| Reverse Polarity Protection | Yes | ||
| Input Range | +10 ~ +30 VDC | ||
| Consumption | 1.8 W | ||
| Mechanical | |||
| Dimensions (L x W x H) | 123 mm x 72 mm x 35 mm | ||
| Installation | DIN-Rail or Wall Mounting | ||
| Environment | |||
| Operating Temperature | -25 to +75°C | ||
| Storage Temperature | -40 to +85°C | ||
| Humidity | 10 to 95% RH, Non-condensing | ||
Ordering information
| I-7021 CR | 1-channel 12-bit Analog Output Module using the DCON Protocol (Blue Cover) (RoHS) |
| I-7021-G CR | 1-channel 12-bit Analog Output Module using the DCON Protocol (Gray Cover) (RoHS) |
| I-7021P CR | 1-channel 16-bit Analog Output Module using the DCON Protocol (Blue Cover) (RoHS) |
| I-7021P-G CR | 1-channel 16-bit Analog Output Module using the DCON Protocol (Gray Cover) (RoHS) |
| M-7021A-G | 1-channel 12-bit Analog Output Module using the DCON and Modbus Protocols (Gray Cover) (RoHS) |