Module 4/8 kênh đầu vào bộ đếm/tần số/vòng quay ICP DAS I-87084W
Features
- 8 Up Counter/Frequency Channels or 4 Encoder Input Channels
- Programmable Digital Filter
- Isolated or Non-isolated Input
- 32-bit Counter
- Individual Channel Configuration
- Virtual Battery Backup to Preserve Counter Values
- Maximum Frequency of up to 1 MHz
- +/-4 kV ESD Protection
- Preset Values for Counter Input
- RoHS Compliant
- Wide Operating Temperature Range: -25 ~ +75°C
Introduction
The I-87084W-G is a 32-bit high-speed Counter/Frequency/Encoder input module that offers a variety of mode options, including “Up Counter”, “Frequency Input”, “Up/Down Counter”, “Direct/Pulse Counter” and “A/B Phase Counter” modes. The mode combinations can be individual set for all 8 channels, where some channels can be set to “Up Counter” mode and other channels can be simultaneously set to “Frequency”, “Up/Down Counter” or “Encoder input” mode. The built-in digital filter is valid for both non-isolated and isolated and can filter out noise where the high/ low pulse width is smaller than the minimum high/low width of the digital filter. The I-87084W-G provides a virtual battery backup function in counter mode, and isolated or non-isolated mode is jumper-selectable.
Applications
Counter Measurement, Frequency Measurement and Encoder Motion Control.
I/O Specifications
| Communication | |
| Interface | RS-485 |
| Format | N, 8, 1 |
| Baud Rate | 1200 ~ 115200 bps |
| Protocol | DCON |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicators/Display | |
| System LED Indicator | 1 LED as Power/Communication Indicator |
| I/O LED Indicator | 8 LEDs as Digital Input Indicators |
| Isolation | |
| Intra-module Isolation, Field-to-Logic | 2000 VDC |
| EMS Protection | |
| ESD (IEC 61000-4-2) | 4 kV Contact for Each Terminal |
| ±8 kV Air for Random Point | |
| Power | |
| Power Consumption | 0.6 W |
| Mechanical | |
| Dimensions (W x L x H) | 30 mm x 102 mm x 115 mm |
| Environment | |
| Operating Temperature | -25 ~ +75°C |
| Storage Temperature | -40 ~ +85°C |
| Humidity | 10 ~ 95% RH, Non-condensing |
System Specifications
| Counter/Frequency/Encoder Input | ||
| Channels | 4-channel Up/Down Counter (CW/CCW) 4-channel Dir/Pulse Counter (Bi-direction) 4-channel A/B Phase (Quadrature Counting) 8-channel Up Counter 8-channel Frequency |
|
| Contact | Wet | |
| Sink/Source (NPN/PNP) | Sink | |
| Types | Counter, Frequency or Encoder | |
| Counter/Encoder-bits | 32-bit (4,294,967,295) | |
| Isolated | On Voltage Level | +3.5 VDC ~ +30 VDC |
| Off Voltage Level | +1 VDC Max. | |
| Non-isolated | On Voltage Level | +2.4 VDC ~ +5 VDC |
| Off Voltage Level | +0.8 VDC Max. | |
| Programmable Digital Filter | 1 ~ 32767 μs | |
| Individual Channel Configuration | Yes | |
| Counter Mode | Up or Up/Down | |
| Encoder Mode | CW/CCW, Dir/Pulse, AB Phase | |
| Frequency Mode | Yes | |
| Max. Speed | Isolated | 3.5 VDC ~ 10 VDC: 200 kHz 10 VDC ~ 30 VDC: 150 kHz |
| Non-isolated | 1 MHz | |
| Frequency Accuracy | 1 Hz~200 kHz = ±0.025% of Input Frequency (Note1) 200 kHz~1 MHz =±0.1% of Input Frequency |
|
| Virtual Battery Backup to preserve Counter Values |
Yes | |
Note1:
| Frequency Range | Frequency Error (typical) |
| 1 Hz ~ 10 Hz | 0.01 Hz |
| 10 Hz ~ 10 KHz | 0.5 Hz |
| 10 KHz ~ 100 KHz | 15 Hz |
| 100 KHz ~ 200 KHz | 30 Hz |
Odering information
| I-87084W-G CR | 4-/8-channel Counter/Frequency/Encoder Module (Gray Cover) (RoHS) |