Module RS-485 DCON & Modbus 8 kênh đầu vào số (DI) + 8 kênh đầu ra số (DO) ICP DAS M-7055D
Features
- I-7055(D)/M-7055(D)
- Source-type Digital Output Channels with Overload Protection
- I-7055(D)-NPN/M-7055(D)-NPN
- Sink-type Digital Output Channels with Overload Protection
- All Digital Input Channels can be used as 16-bit Counters
- Short Circuit Protection
- 4 kV ESD Protection
- 3750 VDC Intra-module Isolation
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
- Wide Operating Temperature Range: -25 ~ +75°C
Introduction
The I-7055 offers 8 isolated channels for digital input and 8 isolated channels for digital output. Either sink-type or source-type digital input can be selected via wire connections. All digital input channels are also able to be used as 16-bit counters. The I-7055 supports source-type output with short circuit protection. There are options to enable both power-on and safe values. The I-7055D has 16 LED indicators that can be used to monitor the status of the digital input and digital output channels. 4 kV ESD protection and 3750 VDC intra-module isolation are standard. The M-7055 has the same hardware specifications as the I-7055, but provides additional support for the Modbus RTU protocol as well as the DCON protocol.
Specification
| Models | I-7055 | I-7055D | I-7055-NPN | I-7055D-NPN |
| M-7055 | M-7055D | M-7055-NPN | M-7055D-NPN | |
| Communication | ||||
| Interface | RS-485 | |||
| RS-485 Bias Resistor | No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) | |||
| Format | N, 8, 1 | |||
| Baud Rate | 1200 ~ 115200 bps | |||
| Protocol | DCON (for I-7055 series) | |||
| Modbus RTU, DCON (for M-7055 series) | ||||
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) | |||
| LED Indicator/Display | ||||
| System LED Indicator | Yes, 1 LED as Power/Communication Indicator | |||
| I/O LED Indicator | – | Yes, 8 LEDs as Digital Input & 8 LED as Digital Output Indicators |
– | Yes, 8 LEDs as Digital Input & 8 LED as Digital Output Indicators |
| 7-Segment LED Display | – | |||
| Isolation | ||||
| Intra-Module Isolation, Field-to-Logic | 3750 VDC | |||
| EMS Protection | ||||
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal | |||
| ±8 kV Air for Random Point | ||||
| EFT (IEC 61000-4-4) | ±4 kV for Power Line | |||
| Surge (IEC 61000-4-5) | ±3 kV for Power Line | |||
| Power | ||||
| Reverse Polarity Protection | Yes | |||
| Input Range | 10 ~ 30 VDC | |||
| Consumption | 0.8 W | 1.6 W | 1.2 W | 2.2 W |
| Mechanical | ||||
| Dimensions (W x L x H) | 72 mm x 123 mm x 35 mm | |||
| Installation | DIN-Rail or Wall Mounting | |||
| Environment | ||||
| Operating Temperature | -25 ~ +75°C | |||
| Storage Temperature | -40 ~ +85°C | |||
| Humidity | 10 ~ 95% RH, Non-condensing | |||
I/O Specification
| Models | I-7055 | I-7055D | I-7055-NPN | I-7055D-NPN | |
| M-7055 | M-7055D | M-7055-NPN | M-7055D-NPN | ||
| Digital Input/Counter | |||||
| Channels | 8 | ||||
| Type | Dry Contact | Source | |||
| Wet Contact | Sink/Source | ||||
| Wet Contact | On Voltage Level | +10 ~ 50 VDC | |||
| Off Voltage Level | +4 VDC Max. | ||||
| Dry Contact | On Voltage Level | Close to GND | |||
| Off Voltage Level | Open | ||||
| Effective Distance for Dry Contact |
500 m Max. | ||||
| Counters | Max. Count | 65535 (16-bit) | |||
| Max. Input Frequency |
100 Hz | ||||
| Min. Pulse Width | 5 ms | ||||
| Input Impedance | 10 KΩ | ||||
| Channel-to-Channel Isolation | – | ||||
| Overvoltage Protection | ±70 VDC | ||||
| Digital Output | |||||
| Channels | 8 | ||||
| Type | Open Source | Open Collector | |||
| Sink/Source (NPN/PNP) | Source | Sink | |||
| Load Voltage | +10 ~ 40 VDC | +3.5 ~ 50 VDC | |||
| Max. Load Current | 650 mA/Channel | 700 mA/Channel | |||
| Overvoltage Protection | 47 VDC | 60 VDC | |||
| Overload Protection | 1.4 A (with short-circuit protection) | ||||
| Power-on Value | Yes | ||||
| Safe Value | Yes | ||||
Ordering information
| I-7055 CR | 8-channel Isolated Digital Input and 8-channel Isolated Digital Output Module using the DCON Protocol (Blue Cover) (RoHS) |
| I-7055-G CR | 8-channel Isolated Digital Input and 8-channel Isolated Digital Output Module using the DCON Protocol (Gray Cover) (RoHS) |
| I-7055D CR | I-7055 with LED Display (Blue Cover) (RoHS) |
| I-7055D-G CR | I-7055 with LED Display (Gray Cover) (RoHS) |
| I-7055-NPN-G CR | 8-channel Isolated Digital Input and 8-channel Isolated Digital Output Module (Gray Cover) (RoHS) |
| I-7055D-NPN-G CR | I-7055-NPN with LED Display (Gray Cover) (RoHS) |
| M-7055-G CR | 8-channel Isolated Digital Input and 8-channel Isolated Digital Output Module using the DCON and Modbus Protocols (Gray Cover) (RoHS) |
| M-7055D-G CR | M-7055 with LED Display (Gray Cover) (RoHS) |
| M-7055-NPN-G CR | 8-channel Isolated Digital Input and 8-channel Isolated Digital Output Module using the DCON and Modbus Protocols (Gray Cover) (RoHS) |
| M-7055D-NPN-G CR | M-7055-NPN with LED Display (Gray Cover) (RoHS) |