Module 2 cổng Ethernet Modbus TCP 6 kênh đầu vào số (DI) + 6 kênh đầu ra Relay ICP DAS ET-2260
Features
- Built-in Web Server
- Support Modbus TCP/UDP Protocols
- Powerful 32-bit MCU Handles Efficient Network Traffic
- 2-port Ethernet Switch (LAN Bypass) for Daisy-Chain Wiring
- Dual Watchdog
- I/O Pair Connection (Push and Polling)
- Supports web configuration and firmware update via Ethernet
- Built-in I/O
- DI/Counter: 6 channels
- Power Relay: 6 channels
- LED Display to Indicate the I/O status
- Wide Operating Temperature Range: -25 ~ +75 °C
Introduction
Providing various digital I/O functions, the ET-2260 module is an IP-based Ethernet I/O monitoring and control module. The module can be remotely controlled through a 10/100 M Ethernet network by using Modbus TCP/UDP protocol. Modbus has become a de facto standard communications protocol in industry, and is now the most commonly available means of connecting industrial electronic devices. This makes the ET-2260 module perfect integration with the HMI, SCADA, PLC and other software systems.
The ET-2260 provides 6 wet contact Digital Input channels and 6 Form A electromechanical Relays. With 2 Ethernet ports, the ET-2260 allows daisy chain connection which permits the flexibility in locating devices, eases installation and lowers infrastructure costs. It features 8 kV ESD protection, 4 kV EFT protection, 3 kV surge and 3750 VDC I/O isolation are also provided to enhance noise protection capabilities in industrial environments. Each input channel can be used as a 32-bit counter. The power-on value and safe value of relay are configurable.
The module can be used to create DI to DO pair-connect through the Ethernet. After configuration, the ET-2260 module can poll the status of the local DI channels and then use the Modbus/TCP protocol to continuously write to the remote DO devices.
It is equipped with removable terminal block connector for easy and robust wiring in industrial situations, and features a powerful 32-bit ARM MCU to handle efficient network trafficking.
System Specification
| System | |
| CPU | 32-bit ARM |
| Communication | |
| Ethernet Port | 2 x RJ-45, 10/100 Base-Tx, Switch Ports |
| Protocol | Modbus TCP, Modbus UDP |
| Security | Password and IP Filter |
| I/O Pair Connection | Yes (Push, Polling) |
| Dual Watchdog | Yes, Module, Communication (Programmable) |
| LAN Bypass | Yes |
| LED Indicators | |
| For System Running | Yes |
| For Ethernet Link/Ack | Yes |
| For DI/DO status | Yes |
| 2-way Isolation | |
| Ethernet | 1500 VDC |
| I/O | 3750 VDC |
| EMS Protection | |
| ESD (IEC 61000-4-2) | ±8 kV Contact for Each Terminal and ±16 kV Air for Random Point |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| Surge (IEC 61000-4-5) | ±3 kV for Power Line |
| Power Requirements | |
| Reverse Polarity Protection | Yes |
| Powered from Terminal Block | +10 ~ +30 VDC |
| Consumption | 3.3 W (Max.) |
| Mechanical | |
| Dimensions (L x W x H) | 127 mm x 33 mm x 99 mm |
| Installation | DIN-Rail or Wall mounting |
| Environmental | |
| Operating Temperature | -25 ~ +75°C |
| Storage Temperature | -30 ~ +80°C |
| Humidity | 10 ~ 90% RH, Non-condensing |
I/O Specification
| Digital Input/Counter | ||
| Channels | 6 | |
| Contact | Wet Contact | |
| Sink/Source (NPN/PNP) | Sink/Source | |
| On Voltage Level | +5 VDC ~ +50 VDC | |
| Off Voltage Level | + 1 VDC Max. | |
| Input Impedance | 7.5 kΩ | |
| Counters | Max. Count | 4,294,967,295 (32 bits) |
| Max. Input Frequency | 3 kHz | |
| Programmable Digital Filter | 1 ~ 6500 ms (0.08 Hz ~ 500 Hz) | |
| Overvoltage Protection | +70 VDC | |
| Power Relay | ||
| Channels | 6 | |
| Type | Power Relay, Form A (SPST N.O.) | |
| Contact Rating | 5 A @ 250 VAC/24 VDC (Resistive Load) | |
| Min. Contact Load | 10 mA @ 5 V | |
| Operate Time | 10 ms (max.) | |
| Release Time | 5 ms (max.) | |
| Mechanical Endurance | 2 × 107 ops. | |
| Electrical Endurance | 105 ops. | |
| Power-On Value | Yes, Configurable | |
| Safe Value | Yes, Configurable | |
Ordering information
| ET-2260 CR | Ethernet I/O Module with 2-port Ethernet Switch, 6-ch Relay Output and 6-ch DI (RoHS) |