Module ổn định đường truyền RS-485 ICP DAS tM-SG4
Features
- Switch-selectable Pull-high/Pull-low Resistors
- 15-step Switch-selectable Termination Resistor
- LED Indicator for Power/Termination
- DIN-Rail mountable
- Cost-effective
- Wide Operating Temperature Range: -25 °C ~ +75 °C
Introduction
Bạn đang muốn tìm đơn vị phân phối cây bóng mát uy tín để mua cây về trồng quanh nhà mình, tham khảo ngay dịch vụ của Hoàng Nguyên Green nhé.
The tM-SG4 is an optional module that is used to improve the communication of RS-485 network. It provides switch selectable pull-high and pull-low resistors on RS-485 network. It also has 15-step switch selectable termination resistor such that the user can select a proper termination resistor to be connected to the RS-485 network easily. If the RS-485 network is not over 100 meters, the termination resistors are not needed. Otherwise, it may be necessary to insert two termination resistors at both end of the RS-485 network. It is not easy to calculate the value of a termination resistor on the RS-485 network. The best way to do this is to use an oscilloscope to check the RS-485 signal directly. If the impedance match of RS-485 network is OK, the oscilloscope will show a very nice square wave. If these square wave signals are distorted, the user will need to insert two termination resistors at both end of the RS-485 network.

Application

Specification
| RS-485 Interface | |||
| Pull-high/Pull-low Resistance | 1 kΩ, 10 kΩ, 100 kΩ, Switch-selectable | ||
| Termination Resistance | 15 Steps, 65 ~ 560 Ω | ||
| LED Indicators | |||
| Power | 1 Red LED as Power Indicator | ||
| Termination Resistor | 1 Green LED as Termination Indicator | ||
| EMS Protection | |||
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal | ||
| Power Requirements | |||
| Reverse Polarity Protection | Yes | ||
| Powered from Terminal Block | Yes, 10 ~ 30 VDC | ||
| Consumption | 0.5 W Max. | ||
| Mechanical | |||
| Dimensions (W x L x H) | 52 mm x 87 mm x 27 mm | ||
| Installation | DIN-Rail Mounting | ||
| Environment | |||
| Operating Temperature | -25 ~ +75 °C | ||
| Storage Temperature | -40 ~ +85 °C | ||
| Humidity | 10 ~ 90% RH, Non-condensing | ||
| Termination Resistance Settings | ||||
| 120R | 330R | 470R | 560R | Termination Resistance (Ω) |
| ON | ON | ON | ON | 65 |
| ON | ON | ON | OFF | 74 |
| ON | ON | OFF | ON | 76 |
| ON | OFF | ON | ON | 81 |
| ON | OFF | OFF | ON | 99 |
| ON | OFF | ON | OFF | 96 |
| ON | ON | OFF | OFF | 88 |
| ON | OFF | OFF | OFF | 120 |
| OFF | OFF | ON | ON | 144 |
| OFF | ON | ON | OFF | 193 |
| OFF | ON | OFF | ON | 207 |
| OFF | ON | OFF | OFF | 330 |
| OFF | OFF | ON | ON | 256 |
| OFF | OFF | ON | OFF | 470 |
| OFF | OFF | OFF | ON | 560 |
| Pull-high and Pull-low Settings | |||
| 1k | 10k | 100k | RS-485 Data Line Status |
| OFF | OFF | OFF | No pull-high/pull-low on RS-485 data line |
| ON | OFF | OFF | 1k [ pull-high and pull-low |
| OFF | ON | OFF | 10k [ pull-high and pull-low |
| OFF | OFF | ON | 100k [ pull-high and pull-low |
| Termination Resistance On/Off Switch | ||||
| OFF | Termination Resistor do NOT work. | |||
| ON | Termination Resistor is worked, and TR LED is light | |||
Odering information
| tM-SG4 CR | RS-485 Pull-high/Pull-low and Termination Resistor Module (RoHS) |