Module 4 kênh phát hiện rò rỉ chất lỏng kết nối RS-485 Modbus RTU ICP DAS iSN-104 CR
Features
- 4-ch Liquid Leak Detection
- Liquid Leakage and cable break detection triggers and audible alarm
- A mute switch to silence the audible alarm
- Five LED indicators to display the status of the power and the alarm
- Liquid Leak Detection Cable and Leader Cable can be up to 500 meters
- Sensitivity adjustable
- Supports the DCON and the Modbus RTU Protocols
Introduction
The iSN-104 Liquid Leak Detection Module is a low-cost intelligent liquid leak detection device that can be used to directly control triggers and audible alarm. No additional conversion module is needed and the iSN-104 can be easily integrated with a variety of monitoring systems to achieve remote alarm and remote device control. The iSN-104 Liquid Leak Detection module can be used to monitor double-core leader cable lengths of up to 500 meters, and can be used with both the extended cable and its included liquid leak detection cable. The module can be easily integrated with other collection hosts connected to the network. The iSN-104 is suitable for real-time leak detection in critical locations, such as computer room base stations, warehouses, libraries, museums and industrial sites, and also for air handling equipment, refrigeration units, liquid containers, or pump tanks, etc., where there is a need to monitor any leakage of the equipment.
When required, communication with the iSN-104 can be programmed based on the Modbus RTU protocol, with the added benefit that different addresses can be configured via hardware to allow for Modbus RTU communication.
2. Work with the water leakage probe that installed in fixed possible leak locations to detect.

| EMS Protection | |
|---|---|
| EFT (IEC 61000-4-4) | ±4 kV for Power |
| ESD (IEC 61000-4-2) | ±8 kV Air for Random Point |
| LED Indicators | |
|---|---|
| Status | 1 as Power Indicator 4 as Alarm Indicator |
| System | |
|---|---|
| Alarm | For both liquid leak detection and cable-break detection. |
| Buzzer | Yes. Can be muted by a push button. |
| Liquid Leak Detection | |
|---|---|
| Channels | 4 |
| Liquid Type | Water, 2uS/cm |
| Sensor Type | Probe for point detection or Cable for line detection |
| Max. Cable Length | 500 meters Includes liquid leak detection cable and extended cable. |
| Sensitivity Range | 26 KΩ ~ 580 KΩ (rotary switch adjustable) |
| Cable-break Detection | Yes. For sense cable CA-LLD-DC100X-Lxxx only. |
| COM Ports | |
|---|---|
| Ports | 1 x RS-485 |
| Baud Rate | Software Configuration: 1200 ~ 115200 bps |
| Data Format | (N,8,1), (O,8,1), (E,8,1), (N,8,2) |
| Protocol | Modbus RTU or DCON |
| Power | |
|---|---|
| Reverse Polarity Protection | Yes |
| Input Range | 10 ~ 30 VDC |
| Consumption | 1.6 W Max. |
| Mechanical | |
|---|---|
| Dimensions (mm) | 72 x 95 x 57 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
|---|---|
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80°C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Ordering Information
| iSN-104 CR | 4-channel Liquid Leak Detection Module, Supports Modbus/RTU and DCON protocols (RoHS) |