Bộ lập trình PLC Cimon CM3-SB16MDT (DI8/DO8, USB Loader, RS232C, No expansion)
8 kênh đầu vào số (DI) + 8 kênh đầu ra số (DO), Truyền thông 1 cổng RS-232, 1 cổng RS-485
Tính năng
- 20Kpps High Speed Counter (2Channel) Built-in.
2PH. 2/4Multi. Input mode possible, Voltage input type (Open collector)
- Max. 2communications can work simultaneously.(RS232, RS485)
CIMON HMI, MODBUS RTU/TCP, PLC Link, Protocol program(User protocol),
Loader protocol, Remote access & Upload/Download supported.
- Memory (10K Step)
- Data preserved in case of power failure.
Built-in Flash memory enabling permanent backup of program without power.
Thông số kĩ thuật
Items | Specification | Remark | |
Power | DC12-24V / 2.16W (In case of maximum expansion) | ||
Program Control Method | Cyclic execution of stored program, Time Driven Interrupt | ||
I/O Control Method | Indirect method, Directed by program instruction | ||
Program language | LD(Ladder Diagram), IL(Instruction List), SFC(Sequential Function Chart) | ||
Data Processing Method | 32 Bit | ||
Instructions | Sequence | 55 Instruction | |
Application | 389 Instruction | ||
Processing speed (Sequence) | 300ns / Step | ||
Program capacity | 15K Step | ||
Maximum I/O points | DI 8points / DO 8points | ||
Operation mode | Run, Stop, Remote Run, Remote Stop | ||
Back-up method | K address by (Latch) parameter | ||
Total program | 128 | ||
Programtypes | Scan | Scan, Subroutine, Periodic Interrupts | |
Periodic Interrupts |
Maximum 16 scan program (Minimum period : 10ms) | ||
Special | HSC, Positioning, I/O Input Filter | ||
Communication | Serial, Ethernet, MODBUS/RTU Master, MODBUS TCP, High Speed Link | ||
Etc. | SFC, FBD (Funtion Block Diagram: under development) | ||
Self-diagnosis function | Detects delay of scan time, memory, I/O, Battery, Power supply | ||
Devicememory | X | 8 points (X00 – X07) | Bit |
Y | 8 points (Y10 – Y17) | Bit | |
M | 8192 points (M0000 – M511F) | Bit | |
L | 4096 points (L0000 – L255F) | Bit | |
K | 4096 points (K0000 – K255F) | Bit | |
F | 2048 points (F0000 – F127F) | Bit | |
T | 512 points (T0000 – T0511) | Word | |
C | 512 points (C0000 – C0511) | Word | |
S | 100 states x 100 set (00.00 – 99.99) | ||
D | 10000 words (D0000 – D9999) | Word | |
Z | 1024 words (Call Stack : Z0000 – Z0063, Z1000 – Z1063) | Word | |
R | 16 points (Index) | ||
High Speed Counter | 20Kpps, 2 Phase 2Ch.(in case of operating 2Ch simultaneously 10kpps) 1Phase pulse Input + Direction signal |
||
Comm. Channel | Standard : USB Loader, Serial(RS232C) Option : Serial 1Ch(RS485) |