Bộ đo và lưu trữ CO + nhiệt độ + độ ẩm, điểm sương kết nối RS-485 + Ethernet/Wi-Fi Modbus + MQTT ICP DAS CL-201-WF
Features
- Able to record CO, CO2, HCHO, H2S, NH3, TVOC, Temperature, Humidity and Dew Point Measurements
- Non-dispersive Infrared (NDIR) CO2 Senso
- Up to 450,000 records with date and time stamps
- Simple and Powerful Software Utility, iOS APP and Android App Included
- Supports the DCON and Modbus RTU/TCP Protocols
- Supports the MQTT Protocol for Ethernet Interface
- Includes RS-485/Ethernet/Wi-Fi Communication Interfaces
- Relay Output for Alarm or IAQ Device Control
- Compatible with IEEE802.11b/g/n standards
- Includes redundant power inputs: PoE (IEEE 802.3af, Class 1) and DC input
- Support Infrastructure and Limit-AP Modes for Wireless Networks
- Ceiling Mounting or Wall Mounting
Introduction
The CL-200-WF is an IAQ (Indoor Air Quality) monitoring module that includes Wi-Fi, Ethernet and RS-485 interfaces, It provides a WLAN connection which complies with the IEEE802.11b/g/n standards. With the popularity of 802.11 network infrastructure, the modules provide an easy method of incorporating wireless connectivity into monitoring and control systems. The CL-200-WF series of Data Logger devices can be used to record CO, CO2, HCHO, H2S, NH3, TVOC, Temperature, Humidity and Dew Point information, including date and time stamps, and are able to store up to 450,000 downloadable records.
Real-time data can be accessed from the CL-200-WF Data Logger from anywhere and at any time using the free Windows software, the iOS App or the Android App, as long as they are connected to the same local network as the Data Logger.
Support is provided for popular industrial protocols such as DCON, Modbus RTU, and Modbus TCP. For Ethernet interface, it also supports the emerging machine-to-machine (M2M)/)IoT (Internet of Things) connectivity protocol – MQTT. The CL-200-WF Data Logger can be connected via widely used communication interfaces including RS-485, Ethernet, PoE and Wi-Fi, meaning that the device can be easily integrated into existing HMI or SCADA systems, and is easily maintained in a distributed control system.
Supports the MQTT Protocol for IoT Applications Features (Ethernet Interface Only)
The MQTT protocol is designed for the efficient exchange of realtime data between a sensor and a mobile device. It operates via TCP/IP and is in widest use today in “machine-to-machine” (M2M) and “Internet of Things” applications.
Simple and Powerful CL-Real-time data from the CL-200-WF series can be accessed from anywhere and at any time using the WF-IIOT-Utility and iOS App200-WF Utility
The DL300 Utility can be used to configure the modules, monitor real-time data, group CL-200-WF modules so that the status of distribution groups can be viewed and managed. The utility also allows the log data to be downloaded and exported to a .CSV file that can then be imported into any industry-standard software or spread sheet for analysis
Real-time data from the CL-200-WF series can be accessed from anywhere and at any time using the WF-IIOT-Utility and iOS App
Get Real-time Data Anywhere and Anytime
Real-time data from the CL-200-WF data logger can be accessed from anywhere and at any time using the DL300 Utility, the iOS or Android App, or via a regular web browser, as long as they are connected to the same local network as the data logger.
Application
|
|
|
HCHO (Formaldehyde)/VOC Detector Automatic Solution
The HCHO/VOC detector provides an instantaneously warning of toxic formaldehyde, which can be found in a plywood factory, furniture factory and new interior remodelling house commonly.
Indoor or Underground Parking Lot Automatic Monitoring Solution
The air quality automation system for indoor or underground parking lot can use the CL-200-WF series modules to monitor the health and safety information, such as CO, CO2, temperature, humidity and dew point, and more.
System Specification
Model | CL-201-WF | CL-202-WF | CL-203-WF | CL-204-WF | CL-205-WF | CL-206-WF | CL-207-WF | CL-208-WF | |
System | |||||||||
CO Alarm | Yes | – | Yes | – | |||||
CO2 Alarm | – | Yes | Yes | – | |||||
HCHO Alarm | – | Yes | – | Yes | – | ||||
TVOC Alarm | – | Yes | – | Yes | |||||
NH3 Alarm | – | Yes | – | ||||||
H2S Alarm | – | Yes | – | ||||||
RH/Temperature Alarm | Yes | ||||||||
Real Time Clock | Yes | ||||||||
Data Logger | Yes, up to 450,000 records | ||||||||
Relay Output | Form A×1, SPST 30 VDC @ 16 A or 250 VAC @ 16 A | ||||||||
Communication | |||||||||
RS-485 Port | Baud Rate = 1200 ~ 115200 bps | ||||||||
Ethernet Port | 10/100 Base-TX, 8-Pin RJ-45 x1 (Auto-negotiating, Auto-MDI/MDIX, LED indicators) | ||||||||
Security | IP filter (whitelist) and Password (web) | ||||||||
Protocol | Modbus/RTU(RS-485), Modbus TCP(Ethernet, Wi-Fi) and MQTT(Ethernet) | ||||||||
Dual Watchdog | Yes, Module (2.3 seconds), Communication (Programmable) | ||||||||
Wi-Fi Interface | |||||||||
Antenna | Antenna = 1 dBi (PCB Antenna) | ||||||||
Output Power | 18 dBm @ 1 DSSS, 14.5 dBm @ 54 OFDM | ||||||||
Receive Sensitivity | -95.7 dBm @ 1 DSSS, -74.0 dBm @ 54 OFDM | ||||||||
Standard Supported | IEEE 802.11 b/g/n | ||||||||
Wireless Mode | Infrastructure & Limited AP | ||||||||
Encryption | WEP, WPA and WPA2 | ||||||||
Transmission Range | 50 meters (LOS) | ||||||||
Electrical | |||||||||
Powered from Terminal Block | +12 to +48 VDC | ||||||||
Power Consumption | Non-PoE | 1.6 W (Max.) | 1.6 W (Max.) | 1.7 W (Max.) | 1.9 W (Max.) | 1.7 W (Max.) | 1.7 W (Max.) | 2.0 W (Max.) | 1.9 W (Max.) |
PoE | 1.7 W (Max.) | 1.7 W (Max.) | 1.8 W (Max.) | 2.0 W (Max.) | 1.8 W (Max.) | 1.8 W (Max.) | 2.1 W (Max.) | 2.0 W (Max.) | |
Mechanical | |||||||||
Installation | Ceiling Mounting/Wall Mounting | ||||||||
Protection Class | IP20 | ||||||||
Dimensions (D x H) | Ø 150 mm x 53 mm | ||||||||
Environment | |||||||||
Operating Temperature | 0 to +50°C | ||||||||
Storage Temperature | -30 to +75°C | ||||||||
Humidity | 10 to 90% RH, Non-condensing |
I/O Specification
Model | CL-201-WF | CL-202-WF | CL-203-WF | CL-204-WF | CL-205-WF | CL-206-WF | CL-207-WF | CL-208-WF |
CO Measurement | ||||||||
Range | 0 to 1000 ppm (Electrochemical) | – | 0 to 1000 ppm (Electrochemical) | – | ||||
Resolution | 1 ppm | – | 1 ppm | – | ||||
Accuracy | ±5% of measured value | – | ±5% of measured value | – | ||||
Response Time | 30 seconds | – | 30 seconds | – | ||||
Warm-up Time | 300 seconds | – | 300 seconds | – | ||||
CO2 Measurement | ||||||||
Range | – | 0 to 9999 ppm (NDIR) | – | |||||
Resolution | – | 1 ppm | – | |||||
Accuracy | – | ±40 ppm ±3% of measured value | – | |||||
Response Time | – | 120 seconds | – | |||||
Warm-up Time | – | 5 minutes | – | |||||
HCHO Measurement | ||||||||
Range | – | 0 ppb to 2000 ppb (Electrochemical) | – | 0 ppb to 2000 ppb (Electrochemical) | – | |||
Resolution | – | 1 ppb | – | 1 ppb | – | |||
Accuracy | – | – | – | – | – | |||
Response Time | – | ≤60 seconds | – | ≤60 seconds | – | |||
– | 180 seconds | – | 180 seconds | – | ||||
TVOC Measurement | ||||||||
Range | – | 0 to 60000 ppb (MEMS Metal Oxide) | – | 0 to 60000 ppb (MEMS Metal Oxide) | ||||
Resolution | – | 1 ppb | – | 1 ppb | ||||
Accuracy | – | ±15% | – | ±15% | ||||
Response Time | – | 60 seconds | – | 60 seconds | ||||
Warm-up Time | – | 180 seconds | – | 180 seconds | ||||
NH3 Measurement | ||||||||
Range | – | 0 to 100 ppm (Electrochemical) | – | |||||
Resolution | – | 1 ppm | – | |||||
Accuracy | – | ±5% of measured value | – | |||||
Response Time | – | <120 Sec | – | |||||
Warm-up Time | – | 180 Sec | – | |||||
H2S Measurement | ||||||||
Range | – | 0 to 100 ppm (Electrochemical) | – | |||||
Resolution | – | 1 ppm | – | |||||
Accuracy | – | ±5% of measured value | – | |||||
Response Time | – | <120 Sec | – | |||||
Warm-up Time | – | 180 Sec | – | |||||
Temperature Measurement | ||||||||
Range | -10 to +50°C | |||||||
Resolution | 0.1°C | |||||||
Accuracy | ±0.6°C | |||||||
Relative Humidity Measurement | ||||||||
Range | 0 to 100% RH, Non-condensing | |||||||
Resolution | 0.1% RH, Non-condensing | |||||||
Accuracy | ±5% RH, Non-condensing | |||||||
Dew Point | ||||||||
Range | Calculated using temperature and relative humidity | |||||||
Resolution | 0.1°C |
Installation
CL-2xx-E + RJ45 Cable:
CL-2xx-E (Ethernet Type) are with optional angle-bent RJ45 cable to smoothly install the Ethernet plug in the hole of the ceiling-mounted
Ordering information
CL-201-WF CR NEW | Remote CO/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi Interfaces and PoE (RoHS) |
CL-202-WF CR NEW | Remote CO2/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi Interfaces and PoE (RoHS) |
CL-203-WF CR NEW | Remote CO/CO2/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi Interfaces and PoE (RoHS) |
CL-204-WF CR Available soon | Remote HCHO/TVOC/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi Interfaces and PoE (RoHS) |
CL-205-WF CR Available soon | Remote NH3/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi Interfaces and PoE (RoHS) |
CL-206-WF CR Available soon | Remote H2S/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi Interfaces and PoE (RoHS) |
CL-207-WF CR Available soon | Remote HCHO/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi Interfaces and PoE (RoHS) |
CL-208-WF CR Available soon | Remote TVOC/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi Interfaces and PoE (RoHS) |
Accessories
EWB-C150 | External Wall Box for CL-200 series |
CA-RJ45-04 | RJ45 Cable, Male-Female, 30cm (90º) |