Bộ lập trình nhúng CANopen 8 cổng I/O Expansion ICP DAS CAN-8823
CANopen, a kind of communication protocols, is based on the intelligent field bus (CAN bus). It was developed as a standardized embedded network with highly flexible configuration capabilities. It provides standardized communication objects for real-time data (Process Data Objects, PDO), configuration data (Service Data Objects, SDO), network management data (NMT message, and Error Control), and special functions (Time Stamp, Sync message, and Emergency message). By now, CANopen is used in many various application fields, such as medical equipment, off-road vehicles, maritime electronics, public transportation, building automation and etc.
CAN-8823 main control unit is specially designed for the slave device of CANopen protocol. It follows the CANopen Spec DS-301 V4.02 and DSP-401 V2.1, and supplies many features for users, such as dynamic PDO, EMCY object, error output value, SYNC cyclic and acyclic, … and etc. In order to expand I/O channel more flexible, an CAN-8823 supports up to 8 slots for I/O expansion and suits with a lot of ICP DAS DI / AI / DO / AO modules. User can choose DI/DO/AI/AO modules of I-87K series or I-8000 series to fit the customized practice applications. In addition, we also provide CAN-8823 Utility to allow users to create the EDS file dynamically. The EDS file is based on CANopen DSP-306 and can be compatible with different CANopen master interfaces. The application architecture is as follows.

Applications
|
![]() |
Utility
CAN-8823 can automatically scan the I-8K/I-87K IO modules plugged in the main unit and assigned these modules to the specific application. Before users apply the CAN-8823 in CANopen applications, they must understand the relationship between these CANopen application and device object dictionary in CAN-8823.
We also provide the CAN-8823 Utility tool to allow users to make the configuration of AI/AO modules and some CANopen communication parameters, such as Rx and Tx PDO mapping, error control, and device object dictionary. After finishing the Utility configuration, it will create the EDS file for the connected CAN-8823 device. Furthermore, the EDS file of the CAN-8823 is not needed for the application, user can use the default configuration for general DI/DO/AI/AO. And users only need to set the Node ID and baud by hardware rotary switch. Then, after wire connection and the CAN-8×23 powered on, it can work normally on the CAN bus network through CANopen protocol.

Design FlowChart
The following simple steps show how to use CAN-8823 in CANopen protocol.

Features
|
NMT
|
Slave
|
|
Error Control
|
Node Guarding and Heartbeat Producer protocol
|
|
No. of PDOs
|
16Rx , 16Tx
|
|
PDO Modes
|
Event Triggered, Remotely requested, Cyclic and acyclic SYNC
|
|
PDO Mapping
|
Available
|
|
No. of SDOs
|
1 server, 0 client
|
|
Emergency Message
|
yes
|
|
CANopen Version
|
DS-301 v4.02
|
|
Device Profile
|
DSP-401 v2.1
|
|
Baud Rate Setting by Rotary Switch
|
10K, 20K, 50K, 125K, 250K, 500K, 800K, and 1Mbps
|
|
Node ID setting by Rotary Switch
|
yes
|
|
Produce EDS file Dynamically
|
yes
|
|
ERR, RUN,and PWR LED
|
yes
|
Module Support
|
Type
|
I-8K Series I/O
|
I-87K Series I/O
|
Type
|
I-8K Series I/O
|
I-87K Series I/O
|
|
High Profile
|
High Profile
|
High Profile
|
High Profile
|
||
|
AI module
|
I-8017HW
|
I-87005W
|
DI module
|
I-8040W
|
I-87040W
|
|
I-8017HS
|
I-87013W
|
I-8040PW
|
I-87040PW
|
||
|
I-87015W
|
I-8046W
|
I-87046W
|
|||
|
I-87015PW
|
I-8048W
|
I-87051W
|
|||
|
I-87016W
|
I-8051W
|
I-87052W
|
|||
|
I-87017W
|
I-8052W
|
I-87053W
|
|||
|
I-87017W-A5
|
I-8053W
|
I-87053PW
|
|||
| I-87017W-RMS |
I-8053PW
|
I-87053W-A5
|
|||
| I-87017DW |
I-8058W
|
I-87053W-AC1
|
|||
| I-87017ZW |
I-87053W-E5
|
||||
|
I-87017RW
|
I-87058W
|
||||
|
I-87017RCW
|
I-87059W
|
||||
|
I-87018W
|
|||||
| I-87018PW | |||||
|
I-87018RW
|
AO module
|
I-8024W
|
|||
|
I-87018ZW
|
I-87024W
|
||||
| I-87019RW | I-87024DW | ||||
| I-87019PW | I-87024UW | ||||
|
I-87019ZW
|
I-87028UW
|
||||
|
DO module
|
I-8037W
|
I-87037W | I-87028VW | ||
|
I-8041W
|
I-87041W
|
I-87028VW-20V | |||
|
I-87057W
|
|||||
| I-87061W | |||||
|
I-8041AW
|
I-87064W
|
||||
|
I-8056W
|
I-87065W
|
DI & DO module
|
I-8042W
|
I-87054W
|
|
|
I-8057W
|
I-87066W
|
I-8050W
|
I-87055W
|
||
|
I-8060W
|
I-87068W
|
I-8054W
|
I-87063W
|
||
|
I-8064W
|
I-87069W
|
I-8055W
|
|||
|
I-8068W
|
I-8063W
|
||||
|
I-8069W
|
Counter module
|
I-8084W
|
|||
|
PWM module
|
I-8088W
|
Hardware Specifications
|
Hardware
|
|
|
CPU
|
80186, 80 MHz or compatible
|
|
SRAM/Flash/EEPROM
|
512 KB / 512 KB / 2 KB
|
|
NVRAM
|
31 bytes (battery backup, data valid for up to 10 years)
|
|
RTC (Real Time Clock)
|
Yes
|
|
Watchdog
|
Watchdog IC
|
|
Expansion Slot
|
8 slots
|
|
CAN Interface
|
|
|
Controller
|
NXP SJA1000T with 16 MHz clock
|
|
Transceiver
|
NXP 82C250
|
|
Connector
|
5-pin screwed terminal block (N/A, CAN_L, CAN_SHLD, CAN_H, N/A)
|
|
Baud Rate (bps)
|
10 k, 20 k, 50 k, 125 k, 250 k, 500 k, 800 k, 1 M (By rotary switch)
|
|
Transmission Distance (m)
|
Depend on baud rate (for example, max. 1000 m at 50 kbps )
|
|
Isolation
|
3000 VDC for DC-to-DC, 2500 Vrms for photo-couple
|
|
Terminator Resistor
|
Jumper for 120 Ω terminator resistor
|
|
Specification
|
ISO-11898-2, CAN 2.0A
|
|
Protocol
|
CANopen DS-301 ver4.02, DS-401 ver2.1
|
|
UART Interface
|
|
|
COM 1
|
RS-232 (For configuration)
|
|
LED
|
|
|
Round LED
|
PWR LED, RUN LED, ERR LED
|
|
Power
|
|
|
Power supply
|
Unregulated +10 ~ +30 VDC
|
|
Mechanism
|
|
|
Dimensions
|
188mm x 312mm x 91mm (W x L x H)
|
|
Environment
|
|
|
Operating Temp.
|
-25 ~ 75 ℃
|
|
Storage Temp.
|
-30 ~ 80 ℃
|
|
Humidity
|
10 ~ 90% RH, non-condensing
|
Ordering information
|
CAN-8823-G
|
CANopen Remote I/O Unit with 8 Expansions |
Optional Accessories
| 4PCD-002 | EMI Ferrite Split/Snap-On Core |
| M12A-5P-IP68 | Field-Installation A-coded 5-pin Female |