Module CCON Slave 16 kênh đầu ra số DO ICP DAS CAN-2057
CCON protocol is one of the application layer protocol on the CAN bus. It was developed by the ICP DAS Co., LTD.
CCON protocol is a simple and effective protocol for industrial automation applications. Based on the CAN bus layer, it could provide many safe and robust communication mechanisms like arbitration, error detection, error correction and etc. It could help to establish the CAN networking application fast and easily. The CCON I/O modules could reply their own real-time I/O information to the controller at regular intervals automatically. In other word, the controller could acquire all remote modules in short time. It makes the communication more efficient when collecting a lot of remote I/O information.
CAN-2057 module is easy to access the digital Output status and set the configuration by using standard CCON protocol. CAN-2057 has 16-channel isolated sink output, and it can be used to various applications, such as PNP, NPN, TTL, relay contact and so forth. By owing to the CCON masters of ICP DAS, you can quickly build a CCON network to approach your requirements.
Applications

Hardware Specifications
| CAN Interface | |
| Connector | 5-pin screwed terminal block (CAN_GND, CAN_L, CAN_SHLD, CAN_H, CAN_V+) |
| Baud Rate (bps) | 10 k, 20 k, 50 k, 125 k, 250 k, 500 k, 800 k, 1 M |
| Terminator Resistor | Switch for 120 Ω terminator resistor |
| Node ID | 1~99 selected by rotary switch |
| Protocol | CCON ver2.00 |
| Digital Output | |
| Channels | 16 (Sink) |
| Load Voltage | +5 ~ +30 VDC |
| Output Type | Open-Collector |
| Reaction Time | 200 us |
| LED | |
| Round LED | PWR LED, RUN LED, ERR LED |
| Terminal Resister | 1 LED as terminal resister indicators |
| DO LED | 16 LEDs as digital output indicators |
| Power | |
| Input range | Unregulated +10 ~ +30 VDC |
| Power Consumption | 1.5 W |
| Mechanism | |
| Installation | DIN-Rail |
| Dimensions | 32.3 mm x 99 mm x 77.5 mm (W x L x H) |
| Environment | |
| Operating Temp. | -25 ~ +75 ℃ |
| Storage Temp. | -30 ~ +80 ℃ |
| Humidity | 10 ~ 90% RH, non-condensing |
Ordering Information
|
CAN-2057
|
CCON module of 16-channel Isolated Open-collector Digital Output
|