Module Zigbee 8 kênh đầu vào số + 8 kênh đầu ra số ICP DAS ZT-2055
Features
- ISM 2.4 GHz Operating Frequency
- Fully Compliant with 2.4G IEEE 802.15.4 / ZigBee Specifications
- Wireless Transmission Range up to 700 m (Default)
- Adjustable RF Transmission Output Power
- External DIP and Rotary Switches for easy Configuration
- GUI Configuration Software (Windows Version)
- Supports AES-128 Encryption for the Wireless Communication (Passive)
- Supports ZigBee Repeater Function
- 8 Digital Input Channels and 8 Digital Output Channels
- All Digital Input Channels can be used as 16-bit Counters
- Sink-type Digital Output Channels with Overload Protection
- Surge and ESD Protection
- Configurable Power-on Value and Safe Value Settings
- DIN-Rail Mountable
Introduction
The ZT-2055 offers 8 isolated channels for digital input and 8 isolated channels for digital output. Either sink-type or source-type digital input can be selected via wire connections. All digital input channels are also able to be used as 16-bit counters. The ZT-2055 supports source-type output with short circuit protection. There are options for configuring power-on and safe digital output values. The ZT-2055 has 16 LED indicators to display the channel status, and has 4 kV ESD protection and 2500 VDC intra-module isolation. Users can easily configure the module address, protocol, checksum, ZB-PID and ZB-channel settings using a combination of rotary and DIP switches.
Application

I/O Specification
| Digital Input/ Counter | ||
| Input Channels | 8 | |
| Input Types | Dry Contact | Source |
| Wet Contact | Sink/Source | |
| Wet Contact | On Voltage Level | +10 VDC ~ +50 VDC |
| Off Voltage Level | Max. +4 VDC | |
| Dry Contact | On Voltage Level | Close to GND |
| Off Voltage Level | Open | |
| Effective Distance for Dry Contact | Max. 500 meters | |
| Counter | Max. Count | 16-bit (65535) |
| Max. Input Frequency | 100 Hz | |
| Min. Pulse Width | 5 ms | |
| Input Impedance | 10 KΩ | |
| Overvoltage Protection | ±70 VDC | |
| Digital Output | ||
| Output Channels | 8 | |
| Output Types | Open Collector | |
| Sink/Source (NPN/PNP) | Sink | |
| Load Voltage | +3.5 ~ 50 VDC | |
| Max. Load Current | 650 mA/Channel | |
| Overvoltage Protection | 60 VDC | |
| Overload Protection | 1.4 A (with short-circuit protection) | |
| Power-on Value | Yes, Programmable | |
| Safe Value | Yes, Programmable | |
System Specification
| Communication Interface | ||
| Wireless Standards | ZigBee 2007 Pro | |
| Transmission Power | 11 dBm (FCC Certificated) (Max. 19 dBm) | |
| 2.4 GHz Antenna | 5 dBi Omni directional | |
| Transmission Range (LoS) | 700 m (Typical) | |
| Certification | FCC/FCC ID, CE (RED excluded) | |
| Max. Slaves in a ZigBee Network | 255 | |
| Protocols | Supports DCON and Modbus RTU Protocols | |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) | |
| LED Indicators | ||
| Power | 1 LED, Red | |
| ZigBee Communication | 1 LED, Green | |
| Digital Input and Output | 8 Green LEDs for Digital Input 8 Red LEDs for Digital Output |
|
| Isolation | ||
| Intra-module Isolated, Field-to-Logic | 2500 VDC | |
| EMS Protection | ||
| ESD (IEC 61000-4-2) | 4 kV Contact for Power Line, Communication Line and each Channel, 8 kV Air for Random Point |
|
| EFT (IEC 61000-4-4) | 4 kV for Power Line | |
| Surge | 3 kV for Power Line | |
| Power | ||
| Input Voltage Range | +10 VDC ~ +30 VDC | |
| Power Consumption | Max. 2.5 W | |
| Mechanical | ||
| Flammability | Fire Retardant Materials (UL 94V-0 Level) | |
| Dimensions (L x W x H) | 96 mm x 33 mm x 110 mm | |
| Installation | DIN-Rail | |
| Environment | ||
| Operating Temperature | -25 ~ +75°C | |
| Storage Temperature | -30 ~ +80°C | |
| Relative Humidity | 10 ~ 90% RH, Non-condensing | |
Ordering information
| ZT-2055 CR | Wireless 8-channel Isolated Digital Input and 8-channel Isolated Digital Output Module (ZigBee Router) (RoHS) |
| Important Note: ZigBee Data Acquisition modules reguire a ZigBee host converter to coordinate the data transmission path. Remember to order a ZT-2550 or ZT-2570 ZigBee host converter when purchasing ZigBee Data Acquisition Products. | |