Bộ đổi nguồn AC/DC Din-Rail MCTT-NDR-75-24 76.8W, 24VDC, 3.2A
75W Single Output Industrial DIN Rail Power Supply NDR-75 series
Features:
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage/ Over temperature
Cooling by free air convection
Can be installed on DlN rail TS-35/7.5 or 15
UL 508 (industrial control equipment} approved
EN61000-6-2(EN50082-2} industrial immunity level
100% full load burn-in test
1 years warranty
| Model |
NDR-75-12 |
NDR-75-24 |
NDR-75-48 |
| Dc Voltage |
12V |
24V |
48V |
| Rated Current |
6.3A |
3.2A |
1.6A |
| Current Range |
0 ~ 6.3A |
0 ~ 3.2A |
0 ~ 1.6A |
| Rated Power |
75.6W |
76.8W |
76.8W |
| Ripple & Noise (Max.) |
80mVp-p |
120mVp-p |
150mVp-p |
| Voltage Adj. Range |
12 ~ 14V |
24 ~ 28V |
48 ~ 55V |
| Voltage Tolerance |
±2.0% |
±1.0% |
±1.0% |
| Line Regulation |
±0.5% |
±0.5% |
±0.5% |
| Load Regulation |
±1.0% |
±1.0% |
±1.0% |
| Setup, Rise Time | 1200ms, 60ms/230VAC 2000ms, 60ms/115VAC at full load | ||
| Hold Up Time | 60ms/230VAC 12ms/115VAC at full load | ||
| Voltage Range | 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)] | ||
| Frequency Range | 47 ~ 63Hz | ||
| Efficiency |
85.50% |
88% |
89% |
| Ac Current | 1.45A/115VAC 0.9A/230VAC | ||
| Inrush Current | 20A/115VAC 35A/230VAC | ||
| Leakage Current | <1mA / 240VAC | ||
| Overload | 105 ~ 130% rated output power | ||
| Protection type : Constant current limiting, recovers automatically after fault condition is removed | |||
| Over voltage |
14 ~ 17V |
29 ~ 33V |
56 ~ 65V |
| Protection type : Shut down o/p voltage, re-power on to recover | |||
| Over Temperature | Protection type : Shut down o/p voltage, re-power on to recover | ||
| Working Temp. | -20 ~ +70℃ (Refer to “Derating Curve”) | ||
| Working Humidity | 20 ~ 95% RH non-condensing | ||
| Storage Temp., Humidity | -40 ~ +85℃, 10 ~ 95% RH | ||
| Temp. Coefficient | ±0.03%/℃ (0 ~ 50℃) | ||
| Vibration | Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | ||
| Withstand Voltage | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | ||
| Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH | ||
| Emc Emission | Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020 | ||
| Emc Immunity | Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, EAC TP TC 020 | ||
| Mtbf | 486.2K hrs min. MIL-HDBK-217F (25℃) | ||
| Dimension | 32*102*125.2mm( L*W*H) | ||
| Packing | 0.51Kg; 28pcs/15.3Kg/1.22CUFT | ||
| Note | |||
| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. | |||
| 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. | |||
| 3. Tolerance : includes set up tolerance, line regulation and load regulation. | |||
| 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. | |||