Cảm biến phát hiện rò rỉ nước RS-485 Modbus ICP DAS iSN-101 CR
Features
- 1-ch Liquid Leak Detection
- Liquid Leakage detection triggers and audible alarm
- A mute button to silence the audible alarm
- Two LED indicators to display the status of the power and the alarm
- Relay Output for Liquid Leakage Alarm
- Liquid Leak Detection Cable and Leader Cable can be up to 500 meters
- Sensitivity adjustable
- Supports the DCON and the Modbus RTU Protocols
Introduction
The iSN-101 Liquid Leak Detection Module is a low-cost intelligent liquid leak detection device that can be used to directly control Relay Output. No additional conversion module is needed and the iSN-101 can be easily integrated with a variety of monitoring systems to achieve remote alarm and remote device control. The iSN-101 Liquid Leak Detection module can be used to monitor double-core leader cable lengths of up to 500 meters, and can be used with both the extended cable and its included liquid leak detection cable. If liquid is detected, the controller immediately activates the output relay – the normally open, normally closed passive output signal . The module can be easily integrated with other collection hosts connected to the network. The iSN-101 is suitable for real-time leak detection in critical locations, such as computer room base stations, warehouses, libraries, museums and industrial sites, and also for air handling equipment, refrigeration units, liquid containers, or pump tanks, etc., where there is a need to monitor any leakage of the equipment.
When required, communication with the iSN-101 can be programmed based on the Modbus RTU protocol, with the added benefi t that different addresses can be confi gured via hardware to allow for Modbus RTU communication.
Applications
2. Work with the water leakage probe that installed in fi xed possible leak locations to detect.

Specifications
| EMS Protection | |
|---|---|
| EFT (IEC 61000-4-4) | ±4 kV for Power |
| ESD (IEC 61000-4-2) | ±8 kV Air for Random Point |
| LED Indicators | |
|---|---|
| Status | 1 as Power Indicator 1 as Alarm Indicator |
| System | |
|---|---|
| Alarm | For both liquid leak detection and cable-break detection. |
| Buzzer | Yes. Can be muted by a push button. |
| Relay Output | Signal Relay, Form A x1, SPST 0.5 A @ 125 VAC 2 A @ 30 VDC |
| Liquid Leak Detection | |
|---|---|
| Channels | 1 |
| Liquid Type | Water, 2uS/cm |
| Sensor Type | Probe for point detection or Cable for line detection |
| Max. Cable Length | 500 meters Include Liquid Leak Detection Cable and Extended Cables. |
| Sensitivity Range | 26 KΩ ~ 580 KΩ (adjustable by rotary switch) |
| Cable-break Detection | Yes. For sense cable CA-LLD-DC100X-Lxxx only. |
| COM Ports | |
|---|---|
| Ports | 1 x RS-485 |
| Baud Rate | Software Configuration: 1200 ~ 115200 bps |
| Data Format | (N,8,1), (O,8,1), (E,8,1), (N,8,2) |
| Protocol | Modbus RTU or DCON |
| Power | |
|---|---|
| Reverse Polarity Protection | Yes |
| Input Range | 10 ~ 30 VDC |
| Consumption | 1.5 W Max. |
| Mechanical | |
|---|---|
| Dimensions (mm) | 83 x 70 x 29 (W x L x H) |
| Installation | Screw Mounting |
| Environment | |
|---|---|
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80°C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Ordering information
| iSN-101 CR | 1-channel Liquid Leak Detection Module, Supports Modbus/RTU and DCON protocols. (Wall mount) (RoHS) |