Module CANopen Slave 8 kênh đầu vào Thermocouple ICP DAS CAN-2018C
CAN-2018C module follows the DS-301 version 4.02 and DSP-401 version 2.1. You can access the thermocouple input status and set the configuration by using standard CANopen protocol. CAN-2018C has passed the validation of the CiA CANopen Conformance Test tool. Therefore, you can use it with standard CANopen master easily by applying the EDS file. CAN-2018C has 8-channel thermocouple input. It can be used to various applications. By owing to the CANopen masters of ICP DAS, you can quickly build a CANopen network to approach your requirements. For more information about the CANopen master interfaces and other CANopen products, please refer to the following web site, please refer to the following web site.
Applications


Hardware Specifications
|
CANopen Interface
|
|
|
NMT
|
Slave
|
|
Error Control
|
Node Guarding protocol / Heartbeat Producer
|
|
No. of PDOs
|
10Rx , 10Tx
|
|
PDO Modes
|
Event Triggered, Remotely requested, Cyclic and acyclic SYNC
|
|
PDO Mapping
|
Available
|
|
No. of SDOs
|
1 server, 0 client
|
|
Emergency Message
|
Yes
|
|
CANopen Version
|
DS-301 v4.02
|
|
Device Profile
|
DSP-401 v2.1
|
|
Specification
|
ISO-11898-2, CAN 2.0A
|
|
Baud Rate (bps)
Setting by Rotary Switch |
10 k, 20 k, 50 k, 125 k, 250 k, 500 k, 800 k, and 1 M
|
|
Node ID
Setting by Rotary Switch |
1 ~ 99
|
|
Terminator Resistor
|
Switch for 120 Ω terminator resistor
|
|
Connector
|
5-pin screwed terminal block (CAN_GND, CAN_L, CAN_SHLD, CAN_H, CAN_V+)
|
|
EDS file
|
Yes
|
|
Analog Input
|
|
|
Channels
|
8
|
|
Input Type
|
+/- 15mV, +/- 50mV, +/- 100mV, +/- 500mV, +/- 1V, +/- 2.5V
+/-20mA,(Requires Optional External 125 Ohm Resistor) Thermocouple (J, K, T, E, R, S, B, N, C) |
|
Resolution
|
16-bit
|
|
Sampling Rate
|
10 Samples/Sec. (Total)
|
|
Accuracy
|
+/-0.1% FSR
|
|
Zero Drift
|
+/- 10 μV/ °C
|
|
Span Drift
|
+/- 25 ppm/ °C
|
|
Common Mode Rejection
|
86 dB
|
|
Normal Mode Rejection
|
100 dB
|
|
Input Impedance
|
>400 kΩ
|
|
Individual Channel Configuration
|
Yes
|
|
Open Thermocouple Detection
|
Yes
|
|
Over voltage Protection
|
240 Vrms
|
|
ESD Protection
|
+/-4kV, Contact for each terminal.
|
|
Intra-module Isolation, Field to Logic
|
3000 VDC
|
|
LED
|
|
|
Power
|
PWR, red
|
|
CANopen Status
|
RUN/ERR, green/orange
|
|
Power
|
|
|
Power Supply
|
Unregulated +10 ~ +30 VDC
|
|
Power Consumption
|
1.5 W
|
|
Mechanism
|
|
|
Installation
|
DIN-Rail
|
|
Dimensions
|
32.3 mm x 99 mm x 77.5 mm ( W x L x H )
|
|
Environment
|
|
|
Operating Temp.
|
-25 ~ 75 ℃
|
|
Storage Temp.
|
-30 ~ 80 ℃
|
|
Humidity
|
10 ~ 90% RH, non-condensing
|
Thermocouple Type
|
Type Code
|
Temperature Range (°C)
|
|
J
|
-210 °C ~ +1200 °C
|
|
K
|
-270 °C ~ +1372 °C
|
|
T
|
-270 °C ~ +400 °C
|
|
E
|
-270 °C ~ +1000 °C
|
|
R
|
-50 °C ~ +1765 °C
|
|
S
|
-50 °C ~ +1765 °C
|
|
B
|
0 °C ~ +1820 °C
|
|
N
|
-270 °C ~ +1300 °C
|
|
C
|
0 °C ~ +2320 °C
|
Ordering Infomation
|
CAN-2018C/S
|
CANopen Slave Module of 8-channel Thermocouple Input Include CAN-2018C module and a CN-1824 daughter board |
Related Products
| PISO-CAN200/200U | 2-Port Isolated Protection CAN Communication Board |
| PISO-CAN400/400U | 4-Port Isolated Protection CAN Communication Board |
| PEX-CAN200i (PISO-CAN200E) |
PCI Express CAN Communication Card |
| PISO-CM100U | One Standalone Intelligent CAN Communication Card |
| PISO-CPM100U | One Standalone Intelligent CANopen Communication Card |
| I-7565-CPM | USB/CANopen Master Converter Module |
| I-8123W | 1 Port High Performance CANopen Master Slot Module |
| I-87123 | 1 Port CANopen Master Slot Module |
| CA-252518D | 25pin Male-Female D-Sub 1.8M flat cable ( 180°) |