Module điều khiển 1 kênh Dimmer + 2 kênh đầu vào số ICP DAS LC-223
Features
- Provide Power Relay Output to turn ON/OFF the Dimming Ballast
- Provide the wall Switch function to Control the Brightness of the Dimming Ballast when the Host Fail Communication
- Isolated Analog Output (0 to 20 mA, 0 to 10 V, 1 to 10 V) For Dimming Control
- Provide The Dry Contact to trigger the Brightness of the Dimming Ballast
- Supports Modbus RTU and DCON Protocols
- 2500 VDC Intra-Module Isolation
- ±4 kV ESD and EFT Protection
- Tiny Form-Factor with Easy Screw and DIN-Rail Mounting
Introduction
The LC-223 is an easy-to-use dimming ballast control module that can be easily installed and operated without requiring specialist knowledge or skills. The brightness of a fluorescent lamp can be controlled using a dimmer, either via digital input or a host controller. The digital input can be used to directly control the light value of the luminous flux in sequence from 10% to 100%, without the need for a remote host controller. 4 kV ESD protection and 2500 VDC intra-module isolation are also provided. When required, communication with the LC-223 is programmable based on the Modbus RTU protocol, with the added benefit that different addresses can be set via hardware configuration.
Applications

I/O Specifications
| Analog Output | ||
| Channels | 1 | |
| Type | 0 to 20 mA, 4 to 20 mA, 0 to 10 V, 1 to 10 V | |
| Resolution | 12-bit | |
| Accuracy | ±0.1% of FSR | |
| DA Output Response Time | 10 ms | |
| Voltage Output Capability | 20 mA | |
| Current Load Resistance | 450 Ω | |
| Digital Input | ||
| Channels | Dry Contact | 2 for the Dimming Trigger |
| Wet Contact | 1 for the Wall Switch Control | |
| Type | Wet Contact, Dry Contact | |
| Wet | ON Voltage Level | 80 VAC to 240 VAC |
| OFF Voltage Level | 30 VAC Max. | |
| Dry | ON Voltage Level | Close to GND |
| OFF Voltage Level | Open | |
| Relay Output | ||
| Channels | 1 | |
| Type | Power Relay, Form A (SPST N.O.) | |
| Operating Voltage | 250 VAC or 30 VDC | |
| Max. Load Current | 16 A (Res. load) | |
| Operate Time | 15 ms Max. | |
| Release Time | 5 ms Max. | |
| Mechanical Endurance | 10,000,000 OPS | |
| Electrical Endurance | 50,000 OPS | |
| Power-on and Safe Value | Yes, programmable | |
System Specifications
| Communication | |
| Interface | RS-485 |
| Format | N, 8, 1 |
| Baud Rate | 1200 to 115200 bps |
| Protocol | DCON, Modbus RTU |
| Node Addresses | 64 to 95 |
| LED Display | |
| Power | 1 LED as Power Indicator |
| Isolation | |
| Intra-module Isolation, Field-to-Logic | 2500 VDC |
| EMS Protection | |
| ESD (IEC 61000-4-2) | ±4 kV contact for each Terminal |
| ±4 kV Air for Random Point | |
| EFT (IEC 61000-4-4) | ±4 kV for Power |
| Power | |
| Reverse Polarity Protection | Yes |
| Powered from Terminal Block | Yes, 10 to 30 VDC |
| Consumption | 1.4 W Max. |
| Mechanical | |
| Dimensions (W x L x H) | 52 mm x 98 mm x 27 mm |
| Installation | Screw Mounting |
| Environment | |
| Operating Temperature | -25 to +75°C |
| Storage Temperature | -30 to +80°C |
| Humidity | 10 to 95% RH, Non-condensing |
Ordering Information
| LC-223 CR | 1-channel Dimmer Control Module with 2-channel Dry Contact Input Trigger (RoHS) |
| LC-223/DIN CR | 1-channel Dimmer Control Module with 2-channel Dry Contact Input Trigger (DIN Rail mount) (RoHS) |
Accessories
| tM-7520U CR | RS-232 to RS-485 converter (RoHS) |
| tM-7561 CR | USB to RS-485 converter (RoHS) |
| I-7514U CR | 4-channel RS-485 Hub (RoHS) |