Bộ lập trình nhúng IoT và lưu trữ dữ liệu (Data Logger) truyền tin nhắn SMS ICP DAS WISE-5801
Introduction
WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the effort and cost spent on system development.
WISE-5801 supports an I/O expansion bus to implement various I/O functions such as D/I, D/O, A/D and D/A according to the XW-Board. In addition, it also support ICP DAS I-7000 / M-7000 remote I/O modules and Modbus RTU slave devices. Based on the variety I/O module of I-7000 / M-7000 and the connection ability with Modbus RTU slave devices, WISE-5801 can provide user more flexibility in application field.
WISE-5801 supports Modbus TCP/RTU protocol to make seamless integration with SCADA software available. It include all advantages which WISE series controllers can provide. In addition, WISE-5801 provide data logger function with microSD card, it can record I/O channel value by event trigger or regular time period. The data files can be sent back by Email or FTP. All setting can be completed through browser.
In addition to merits inherited from the existing WISE series, WISE-5801 even provides more supports in I/O functions. It allows to connecting with a wide range of XW-Boards, I-7000 / M-7000 Remote I/O modules and Modbus RTU slave devices that enables users to freely choose the most suitable I/O modules. With the microSD card, it provides Data Logger function to real-time record the I/O data of the controller and send the data files by FTP or Email at a scheduled time to the control center for further administration management or data analysis. WISE-5801 also features SMS sending function for alarm report and SMS command receiving function.

Feature
- Built-in Web Server for IF-THEN-ELSE rule setting
- Built-in IF-THEN-ELSE rule enigne for logic operation
- Support IO, Counter, Timer, Schedule, Email, Recipe operations
- No more programming. Just click and get done!
- Data logger and data files send back function supported
- Modbus TCP/RTU Protocol for SCADA Software Seamless
- 10/100 Base-TX Ethernet
- Support XW-Board
- Support I-7000 Remote I/O Modules (Up to 16)
- Support Modbus RTU Slave Devices (Up to 10)
- SNTP Time Synchronization Supported
- Support SMS (GSM: Quad-band 850/900/1800/1900 MHz)
Applications
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc.
Hardware Specifications
| CPU Module | |
| CPU | 16-bit CPU |
| SRAM | 768 KB |
| Flash | 512 KB |
| microSD Expansion | Support up to 32 GB microSDHC card |
| RTC (Real Time Clock) | RTC Provide seconds, minutes, hours, date of week/month; month and year |
| Watchdog Timers | Yes (0.8 second) |
| Communication Ports | |
| Ethernet | RJ-45 x 1, 10/100 Base-TX (Auto-negotiating, Auto MDI/MDI-X, LED indicators) |
| COM 1 | RS-232 (TxD, RxD, RTS, CTS, GND), non-isolated, Speed: 115200 bps max. |
| COM 2 | RS-485 (D2+, D2-), self-tuner ASIC inside, non-isolated, Speed : 115200 bps max. |
| LED Indicators | |
| System LED | Yes (Red) |
| Ethernet Link LED | Yes (Green : Ethernet link detected, Flashing Green : Ethernet packet received) |
| Hardware Expansion | |
| I/O Expansion Bus | Yes |
| SMS Function | |
| Frequency Band | Quad-band 850/900/1800/1900 MHz |
| Mode | Text and Unicode mode |
| Power Requirements | |
| Protection | Power Reverse Polarity Protection |
| Frame Ground | Yes (for ESD Protection) |
| Input Range | 12 ~ 48 VDC |
| Redundant Power Input | Yes |
| Power Consumption | 2.0 W |
| Mechanical | |
| Dimensions (W x H x D) | 91 mm x 132 mm x 52 mm |
| Installation | DIN-Rail |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80 °C |
| Ambient Relative Humidity | 10 ~ 90% RH (non-condensing) |
Software Specifications
| Functions | |
| Rule Configuration Website | Access Web server on WISE controllers to edit and upload logic rules through web browser. |
| 36 IF-THEN-ELSE Logic Rules | 3 IF conditions with AND or OR operators 3 THEN actions and 3 ELSE actions |
| 48 Internal Registers | Hold temporary variables and read/write data via Modbus/TCP address. |
| 12 Timers | Delay / Timing functions. |
| 12 Schedules | Setup prescheduled routine tasks. |
| 12 Emails | Send Email messages to pre-set Email receivers. |
| 12 SMS | Send SMS to pre-set mobile phone numbers. |
| 12 CGI Commands | Send pre-set CGI commands. |
| 12 Recipes | Set up THEN/ELSE action groups. |
| Data Logger | Set up the Data Logger configuration, include the data record format, and data file sending operation. |
| Modbus TCP/RTU Protocol | Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
| IF Conditions | |
| DI Channel | ON、OFF、ON to OFF、OFF to ON、Change |
| AI Channel | = 、> 、< 、 ≥ 、 ≤ (value) |
| Internal Register | |
| DI Counter | = 、> 、< 、 ≥ 、 ≤ (value)、Change |
| Timer | Timeout、Not Timeout |
| Schedule | In Range、Out of Range |
| SMS Command | 0、1 |
| Rule Status | Enable、Disable |
| THEN / ELSE Actions | |
| DO Channel | ON、OFF、Pulse Output (apply to XW-Board only) |
| AO Channel | Change the value |
| Internal Register | |
| DI Counter | Reset |
| Timer | Start、Reset |
| Schedule | Enable、Disable |
| Send | |
| SMS Alarm | |
| CGI Commands | |
| Recipe | Execute |
| Data Logger | Start、Stop、One-Time Log |
| Rule Status | Enable、Disable |
Support I/O Module list
| I/O Type | Functions | Modules | |
| I-7000 Remote I/O Module | AI/AO | Voltage & Current | I-7012, I-7012D, I-7012F, I-7012FD, I-7017, I-7017F, I-7017R, I-7017C, I-7017FC, I-7017RC, I-7017R-A5, I-7017Z |
| Thermocouple | I-7011, I-7011D, I-7011P, I-7011PD, I-7018, I-7018BL, I-7018P, I-7018R, I-7018Z, I-7019R |
||
| RTD | I-7013, I-7013D, I-7015, I-7015P, I-7033, I-7033D | ||
| Thermistor | I-7005 | ||
| Transmitter | I-7014D | ||
| Strain Gauge | I-7016 I-7016D I-7016P I-7016PD | ||
| Analog Output | I-7021, I-7021P, I-7022, I-7024, I-7024R | ||
| DI/DO | DC Digital Input | I-7041, I-7041D, I-7041P, I-7041PD, I-7051, I-7051D, I-7052, I-7052D, I-7053_FG, I-7053D_FG |
|
| AC Digital Input | I-7058, I-7058D, I-7059, I-7059D | ||
| DC Digital Output | I-7042, I-7042D, I-7043, I-7043D, I-7045, I-7045D, I-7045-NPN, I-7045D-NPN |
||
| DC Digital Input & Output | I-7044, I-7044D, I-7050, I-7050D, I-7050A, I-7050AD, I-7055, I-7055D, I-7055-NPN, I-7055D-NPN |
||
| Relay Output | Power Relay Output | I-7060, I-7060D, I-7061, I-7061D, I-7063, I-7063D, I-7065, I-7065D, I-7067, I-7067D |
|
| Solid State Relay Output | I-7063A, I-7063AD, I-7063B, I-7063BD, I-7065A, I-7065AD, I-7065B, I-7065BD |
||
| Photomos Relay Output | I-7066, I-7066D | ||
| Others | Counter/Frequency | I-7080, I-7080D, I-7080B, I-7080BD, I-7088 | |
| DL Series | Temperature and Humidity | DL-100T485, DL-100T485-W | |
| CO2 / Temperature / Humidity | DL-302 | ||
| XW-Board | DI/DO | XW107, XW110 | |
| DI/DO/AI/AO | XW304, XW310, XW310C | ||
| M-7000 / Modbus RTU Slave Module | Coil Output / Discrete Input / Input Register / Holding Register | ||
Ordering Information
WISE-5801 CR
User-defined I/O & Data Logger Module with SMS Function for Modbus RTU or DCON Devices
Accessories
- NS-205 CR : Unmanaged 5-Port Industrial Ethernet Switch
- MDR-20-24 CR : 24V/1A, 24 W Power Supply with DIN-Rail Mounting (RoHS)
- DIN-KA52F CR : 24V/1.04A, 25 W Power Supply with DIN-Rail Mounting (RoHS)