Card ISA 16 kênh đầu vào số (DI) + 16 kênh đầu ra Relay ICP DAS P16R16DIO
Features
- Relay output Channel
- Optically isolated digital input channels
- AC/DC signal input ; AC signal input with filter
- Connector pin assignment is compatible to 725 series
- Power Requirements : 200 mA @ +5 V (max.) ; 260 mA @ +12 V (max.)
- LED indicator for each relay output state
Introduction
The P16R16 DIO is a 16 isolated digital input and 16 relay output interface board designed for control and sensing applications. This interface board is easily installed in any PC/AT/XT.The P8R8 DIO Provides 16 electromechanical relay outputs and 16 optically isolated inputs. The P16R16 DIO has two 37-pin D-Sub Connector and the function is equal to two P8R8DIO.
Application
- Factory Automation
- Product Test
- Laboratory Automation
- Security Control
Software
- DOS sample program(with source codes)
- DLL and OCX SDK for Windows 98/NT/2000
- DLL and OCX SDK for 32-bit Windows XP/2003/Vista/7
- VB/VC/Delphi/BCB sample programs with source codes are included
- LabVIEW toolkit for Windows
- Driver for Linux and DasyLab
Specification
| Digital Input | |
| Isolation Voltage | 5000 Vrms (Channel-Channel & Channel-Ground) |
| Channels | 16 |
| Compatibility | Non-polarized OPTO-isolated |
| Input Voltage | Logic 0: 0 ~ 1 VAC/VDC Logic 1: 5 ~ 24 VAC/VDC |
| Input Impedance | 1.2 KΩ, 0.5 W |
| Response Speed | With filter : 0.05 kHz Without filter : 0.045 MHz |
| Relay Output | |
| Channels | 16 |
| Relay Type | 8 SPDT / 8 SPST |
| Contact Rating | 0.3 A @ 120 VAC/VDC 1 A @ 30 VDC |
| Operate Time | 5 ms (typical) |
| Release Time | 5 ms (typical) |
| Insulation Resistance | 100 MΩ |
| Life | Mechanical: 100,000 ops. (min.) Electrical: 100,000 at 1 A @ 30 V, resistive |
| General | |
| Bus Type | ISA |
| I/O Connector | Female DB37 x 1 |
| Dimensions (L x W x D) | 175mm x 121 mm x 22 mm |
| Power Consumption | 200 mA @ +5 V (max.) 260 mA @ +12 V (max.) |
| Operating Temperature | 0 ~ 60 °C |
| Storage Temperature | -20 ~ 70 °C |
| Humidity | 5 ~ 85% RH, non-condensing |
Ordering information
| P16R16DIO CR | 16-channel Isolated D/I and Relay Output (RoHS) Includes one CA-4037B cable and two CA-4002 D-Sub connectors |