Module 8 kênh đầu vào nhiệt Thermistor + 8 kênh đầu ra số (DO) ICP DAS I-87005W
Features
- Thermistor Input
- Individual Channel Configuration
- Open Wire Detection
- 8-channel Digital Output for Alarm Output
- 3000 VDC Intra-module Isolation
- Overvoltage Protection for Thermistor Input
- User-defined Thermistor Types
- RoHS Compliant
- Wide Operating Temperature Range: -25 ~ +75°C
Introduction
The I-87005W module is used for measuring temperature using a thermistor. The module supports a wide range of thermistors, and features individual channel configuration, which means that eight of the input channels can be individually configured for different kinds of thermistor. In addition, the I-87005W also provides 8 digital output channels that can be used for alarm output, and supports user-defined thermistor types, which can be added by specifying the Steinhart coefficients, if necessary. The inclusion of 3000 VDC intra-module isolation and overvoltage protection for the thermistors on the I-87005W ensures that the module operates at a higher reliability
Applications
- Temperature Measurement
- Environment Monitoring
- Tunnel Monitoring
- Building Monitoring
System Specifications
Communication | |
Interface | RS-485 |
Format | N, 8, 1 |
Baud Rate | 1200 ~ 115200 bps |
Protocol | DCON |
Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicators/Display | |
System LED Indicator | 1 LED as Power/Communication Indicator |
I/O LED Indicator | 16 LEDs as High/Low Alarm Signals |
Isolation | |
Intra-module Isolation, Field-to-Logic | 3000 VDC |
EMS Protection | |
ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
±8 kV Air for Random Point | |
Power | |
Power Consumption | 0.7 W Max. |
Mechanical | |
Dimensions (W x L x H) | 30 mm x 95 mm x 114 mm |
Environment | |
Operating Temperature | -25 ~ +75°C |
Storage Temperature | -40 ~ +85°C |
Humidity | 10 ~ 95% RH, Non-condensing |
I/O Specifications
Thermistor Input | |
Channels | 8 |
Wiring | 2 Wires |
Sensor Type | Precon ST-A3, Fenwell U, YSI L100, YSI L300, YSI L1000, YSI B2252, YSI B3000, YSI B5000, YSI B6000, YSI B10000, YSI H10000, YSI H30000, User-defined |
Resolution | 16-bit |
Accuracy | ±0.1% of FSR |
Sampling Rate | 8 Hz (Total) |
Zero Drift | ±0.5 μV/°C |
Span Drift | ±25 ppm/°C |
Common Mode Rejection | 113 dB |
Normal Mode Rejection | 100 dB |
Input Impedance | >1 MΩ |
Individual Channel Configuration | Yes |
Resistance Measurement | 200 kΩ |
Open Wire Detection | Yes |
Overvoltage Protection | 120 VDC/110 VAC |
Digital Output | |
Output Channels | 8 |
Output Type | Isolated Open-collector |
Maximum Load Current | 700 mA/Channel |
Load Voltage | +5 ~ +50 VDC |
Safe Value | Yes |
Power-on Value | Yes |
Ordering information
I-87005W-G CR | 8-channel Thermistor Input and 8-channel Digital Output Module (Gray Cover) (RoHS) |
Accessories
SG-770 CR | 7-channel Differential or 14-channel Single-ended Surge Protector (RoHS) |